Date |
Text |
2006-10-28 16:40:03 | *** UNSAT 2ND REVIEW *** |
| |
| ** PLEASE SEE SOMEITEMS FROM PREVIOUS REVIEW AND |
| QUESTIONS ON REPSONSE LTR AND NEW NOTE FOR CHANGE IN |
| RISER. |
| |
| ** PLEASE KNOW, AS RESUBMITTED PACKAGE WAS PICKED UP |
| FOR REVIEW, THE ORIGINAL PERMIT APPLICATION FROM THE |
| CONTRACTOR WAS NOT LCOATED IN WITH ALL OTHER PAPERWORK? |
| CALLED AND LEFT A MESSAGE ON BILL RIELLY'S VM TO DROP |
| OFF PERMIT APPLCATION. |
| |
| 1) NOTE: OK, REVISED RISER. |
| |
| 2) NOTE: OK REVISED RISER. |
| |
| 3) NOTE: OK. |
| |
| 4) NOTE: OK, REVISED RISER. |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE: OK, HOWEVER LOAD CALCULATIONS DO INDICATE HOW |
| THE LOADS FOR SHOW WINDOW CIRCUITS WERE DERIVED. PLEASE |
| SEE 220.12A |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE INDICATE NEW OR EXISTING RECEPT'S ABOVE |
| WINDOW'S. (EVERY 12' OR FRACTION THEREOF) |
| 210.62,220.12 |
| |
| 7) NOTE:OK, HOWEVER RESPONSE MENTIONS EXISTING PANEL |
| BEING REPLACED WITH A NEW 150A MAIN DISCONNETC HOWEVER |
| RISER DOES NOT SHOW THIS? SHOWS AND INDICATES EQUIPMENT |
| BEING REMOVED ONLY?? |
| |
| 8) NOTE: OK. |
| |
| 9) NOTE: NO, PLEASE SEE THE TC SYSTEM IS BEING SHOWN |
| HOWEVER THE OVER RIDE DEVICE(S) LOCATED AT THE POINT OF |
| ENTRANCE INTO SPACE AND OVER RIDE DEVICE(S) LOCATED AT |
| LOCATIONS WHERE THE OCCUPANT CAN VISUALLY SEE ALL |
| LIGHTING BEING CONTROLLED. PLEASE SEE SEPARATE SPACES |
| WITH FLR TO CEILING HEIGHT PARTITIONS REQUIRED SEPARATE |
| CONTROL. |
| PLEASE SEE "ST" DEVICE AS SHOWN FOR SOME RMS MENTIONS |
| UP TO 12HRS, HOWEVER PLEASE SEE CODE ONLY PERMITS A MAX |
| OF 4HRS ON TIMER TYPE DEVICES. ON OCC SENSOR TYPE |
| DEVICES IT IS 30 MINS. |
| PLEASE SEE SCHEDULE "A" WAS SUBMITTED WHICH DOES SEEM |
| TO FIT FOR SCOPE OF WORK. PLEASE SEE "B" OR "C". PLEASE |
| ALSO SEE PREVIOUS NOTE WITH RESPECT TO PERFORMANCE |
| CALCULATIONS PER 13-415.2. |
| 13-101.1.3 |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FBC CHAPTER 13 FOR |
| AUTOMATED LIGHTING CONTROLLED REQUIRED. |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND |
| .1.3. |
| PLEASE PROVIDE SCHEDULING, TIMERS, |
| OVER-RIDES AND TYPES OF DEVICES. PLEASE |
| SHOW ALL CONTROL/OVER RIDE LOCATIONS. |
| PLEASE SEE ALL SEPARATE SPACES WITH FLR |
| TO CEILING HEIGHT PARTITIONS, WITH |
| CONTROLS. |
| PLEASE PROVIDE ENERGY CALCULATIONS AS |
| REQUIRED 13-415.1.AB.1, 13-415.2.ABC.1, |
| 415.2.C. |
| |
| |
| |
| 10) NOTE: OK. |
| |
| 11) NOTE:NO, PLEASE SEE RESPONSE SPEAKS OF A/C |
| EQUIPMENT. THIS NOT WAS FOR THE "AIC" RATINGS FOR NEW |
| EQUIPMENT/MAINS/PANELS ECT. PLEASE SEE PANELS ARE NOTED |
| AND SHOWN AT 22K. PLEASE INDICATE FUSE RATING(S). |
| 110.9,240.12 |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE INDICATE THE AIC |
| RATINGS FOR ALL NEW SERVICE |
| MAINS/EQUIPMENT. |
| 110.9 |
| |
| ** NEW NOTE ** |
| |
| 12) NOTE: PLEASE INDICATE VOLTAGE DROP FOR FEEDERS FROM |
| MAIN ELECTRICAL ROOM TO NEW PANEL LOCATIONS. |
| PLEASE SEE 13-413.1.ABC.1.1 |
| |
| |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |
| |
| |