Text |
2006-11-07 09:24:18 | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC EB | | FLORIDA BUILDING CODE 2004 EXISTING BUILDING CODE FBC* | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | 1.)A NOTICE OF COMMENCEMENT MUST BE | | FILED WITH THE CLERK OF COURTS, | | FS713.13. | | | | 2.)ADDRESSED. | | | | 3.)DELCARE LEVEL OF ALTERATION FBC EB | | 3 AND INCLUDE FBC EB IN GOVERNING CODE. | | | | I THINK THAT THERE MAY HAVE BEEN A MISUNDERSTANDING. | | THE REFERENCE IS FOR FBC EB CHAPTER 3, WHICH SPECIFIES | | HOW TO DETERMINE THE LEVEL OF ALTERATION.ARCHITECT | | HAS DECLARED A LEVEL 3, WHICH IS OVER 50% RENOVATION. | | IF THIS IS A LEVEL 3 ALTERATION, SHOW COMPLIANCE WITH | | ALL REQUIREMENTS FOR THE EXISTING BUILDING ON THE PLAN. | | IF NOT, REVISE THE NOTE. | | | | 4.-5.)ADDRESSED. | | | | 6.)SHOW MANEUVERING CLEARANCE, PULL | | SIDE, FOR DOORS 03, 04, 05 FBC11-4.13.6, | | FIGURE 11-25. | | | | THIS WAS ADDRESSED FOR DOOR 3 ONLY.PLEASE ADDRESS FOR | | THE OTHER TWO DOORS OR CALL ME TO DISCUSS. | | | | 7-9.)ADDRESSED. |
|