2006-09-29 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| FBC-2004 CHAPTER 11 |
| FLORIDA ADMINISTRATIVE CODE |
| FLORIDA STATUES |
| |
| 1. ALL SHEETS. THE ARCHITECTS TITLE |
| BLOCK DOES NOT REFLECT THE ADDRESS FOUND |
| ON THE DBPR WEBSITE. FAC 61G1-16.004(1) |
| AND FS 481.2055. (SEE ATTACHED SHEET). |
| |
| 2. ROUTE PLANS TO DBPR HOTEL AND |
| RESTURANT DIVISION FOR REVIEW. MINIMUM 2 |
| SETS OF STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS" |
| REQUIRED FOR REVIEW. |
| SECTION 102.2.1. |
| |
| 3. A GREASE INTERCEPTOR MAY BE REQUIRED. |
| PLEASE CONTACT LYNN MASSON, |
| ENVIRONMENTAL COMPLIANCE (561) 822-2271, |
| FAX (561) 822-2279, OR E-MAIL |
| [email protected]. WASTE ORD. 3434. |
| |
| 4. SHT A-5 PLEASE SHOW COMPLIANCE WITH |
| THE FOLLOWING: |
| A. 11-4.16.5 FLUSH CONTROLS |
| B. 11-4.19.5 FAUCETS |
| |
| 5. SHT P-1 ALL EQUIPMENT & FIXTURES |
| UTILIZED FOR STORAGE, PREPARATION AND |
| HANDLING OF FOOD SHALL DISCHARGE THROUGH |
| AN INDIRECT WASTE PIPE BY MEANS OF AN |
| AIR GAP. SECTION 802.1.1. - FLOOR SINKS |
| ARE REQUIRED PER SECTION 802.3. |
| |
| 6. SHT P-1 PLUMBING NOTES #13 AIR |
| CHAMBERS ARE NOT APPROVED. WATER HAMMER |
| ARRESTORS REQUIRED AT QUICK CLOSING |
| VALVES SHALL BE LOCATED NEAR THE |
| FIXTURES IN AN "EFFECTIVE RANGE", (NOT |
| IN THE CEILING), PER PDI-WH 201 AND |
| MANUF. INSTALLATION INSTRUCTIONS. (ICE |
| MAKERS, DISHWASHERS, ETC). |
| |
| 7. SHT P-1 WATER FILTERS SHALL BE |
| COMPLIANT WITH NSF-42. SUBMIT MANUF. |
| SPECIFICATION SHEETS. |
| |
| 8. SHTS A-6 & P-1. SHT A-6 INDICATES A |
| NEW OVEN, AND SHT P-1 INDICATES A FRYER |
| AND THE OVEN AS RECONNECTING (GAS SIZE |
| AND CAPACITY SAME EXISTING). A GAS |
| PERMIT WILL BE REQUIRED AND THE |
| FOLLOWING INFORMATION WILL BE REQUIRED |
| TO VERIFY COMPLIANCE WITH THE GAS CODE: |
| |
| A. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| |
| B. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE IF BEING USED. |
| |
| C. TYPE OF GAS, (LP OR NATURAL). |
| |
| D. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| |
| E. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| F. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. (FOR |
| ALL NEW EQUIPMENT). |
| |
| H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| VALVE TO BE BELOW CEILING. MANUAL SHUT |
| OFF VALVE TO BE UPSTREAM. UNION TO BE |
| DOWN STREAM OF MANUAL VALVE. (INDICATED |
| AS EXISTING RELOCATING). |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |