Date Text
2006-09-29 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUES
  
 1. ALL SHEETS. THE ARCHITECTS TITLE
 BLOCK DOES NOT REFLECT THE ADDRESS FOUND
 ON THE DBPR WEBSITE. FAC 61G1-16.004(1)
 AND FS 481.2055. (SEE ATTACHED SHEET).
  
 2. ROUTE PLANS TO DBPR HOTEL AND
 RESTURANT DIVISION FOR REVIEW. MINIMUM 2
 SETS OF STAMPED PLANS WITH THE TWO PAGE "WORKSHEETS"
 REQUIRED FOR REVIEW.
 SECTION 102.2.1.
  
 3. A GREASE INTERCEPTOR MAY BE REQUIRED.
 PLEASE CONTACT LYNN MASSON,
 ENVIRONMENTAL COMPLIANCE (561) 822-2271,
 FAX (561) 822-2279, OR E-MAIL
 [email protected]. WASTE ORD. 3434.
  
 4. SHT A-5 PLEASE SHOW COMPLIANCE WITH
 THE FOLLOWING:
 A. 11-4.16.5 FLUSH CONTROLS
 B. 11-4.19.5 FAUCETS
  
 5. SHT P-1 ALL EQUIPMENT & FIXTURES
 UTILIZED FOR STORAGE, PREPARATION AND
 HANDLING OF FOOD SHALL DISCHARGE THROUGH
 AN INDIRECT WASTE PIPE BY MEANS OF AN
 AIR GAP. SECTION 802.1.1. - FLOOR SINKS
 ARE REQUIRED PER SECTION 802.3.
  
 6. SHT P-1 PLUMBING NOTES #13 AIR
 CHAMBERS ARE NOT APPROVED. WATER HAMMER
 ARRESTORS REQUIRED AT QUICK CLOSING
 VALVES SHALL BE LOCATED NEAR THE
 FIXTURES IN AN "EFFECTIVE RANGE", (NOT
 IN THE CEILING), PER PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS. (ICE
 MAKERS, DISHWASHERS, ETC).
  
 7. SHT P-1 WATER FILTERS SHALL BE
 COMPLIANT WITH NSF-42. SUBMIT MANUF.
 SPECIFICATION SHEETS.
  
 8. SHTS A-6 & P-1. SHT A-6 INDICATES A
 NEW OVEN, AND SHT P-1 INDICATES A FRYER
 AND THE OVEN AS RECONNECTING (GAS SIZE
 AND CAPACITY SAME EXISTING). A GAS
 PERMIT WILL BE REQUIRED AND THE
 FOLLOWING INFORMATION WILL BE REQUIRED
 TO VERIFY COMPLIANCE WITH THE GAS CODE:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE IF BEING USED.
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2. (FOR
 ALL NEW EQUIPMENT).
  
 H. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. (INDICATED
 AS EXISTING RELOCATING).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]