Plan Review Notes
Plan Review Notes For Permit 06090092
Permit Number 06090092
Review Stop M
Sequence Number 1
Notes
Date Text
2006-10-13 07:57:06DENIED:
 PLEASE CLARIFY THE FOLLOWING:
 1.PLAN SHEET A-1 INDICATES WEST WALL IS INDICATED AS
 A EXISTING TENANT DEMISING WALL.IS THIS AN EXTERIOR
 WALL OR IS THIS INTERIOR TO THE TENANT SPACE.PLEASE
 CLARIFY IF THIS WILL BE SEPARATED OR PROTECTED BY AN
 ENCLOSURE OR SHAFT?
  
 2.PLAN SHEET M-1 DUCT MISSING FIRE DAMPER FROM
 20"X48" R/A DUCT PENETRATING TENANT DEMISING WALL.
  
 3.PLEASE PROVIDE CLEARANCES FROM THE GREASE DUCT TO
 COMBUSTIBLES.SHOW COMPLIANCE WITH 2004 FMC 506.3.6.
  
 4.PLAN SHEET M-1 INDICATES EF-2 SERVES A COOK LINE
 HOOD TERMINATING ON THE ROOF.THIS IS NOT SHOWN ON
 PLAN SHEET M-1.2.
  
 5.PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THE
 HOOD & GREASE DUCT:
 A) TYPE I OR TYPE II HOOD
 B) INDICATE HOOD & DUCT MATERIAL AND GAUGE 2004
 FMC 507.4, 507.5, 506.3.1.1 & 506.4.
 C) INDCIATE DUCT SIZE AND LAYOUT
 D) AIR VELOCITY THROUGH THE GREASE DUCT SHALL
 COMPLY WITH 2004 FMC 506.3.4
  
 6.PLAN SHEET M-1.2 APPEARS TO HAVE A WALL THAT
 TERMINATES ABOVE THE ROOF THAT SEPARATES RTU-1 & EF-1.
 PER 2004 FMC 306.5, ACCESS SHALL NOT REQUIRE CLIMBING
 OVER OBSTRUCTIONS GREATER THAN 30 INCHES.PLEASE NOTE,
 SHOULD ROOF HAVE A SLOPE GREATER THAN 4/14 PITCH SHOW
 COMPLIANCE WITH 306.5 ITEMS 1 THROUGH 7.
  
 7.PLEASE INDICATE ACCESS TO ROOF.
  
 8.PLEASE CLARIFY WHAT EQUIPMENTTHE20"X48" RETURN
 AIR DUCT & 20"X32" SUPPLY DUCT TERMINATING ON THE ROOF
 GO TO (RTU-1?)
  
 9.ADDITIONAL PERMITS REQUIRED FOR HOOD, FIRE
 SUPPRESSION, & WALK-IN COOLER.PLEASE PROVIDE PLANS
 AND MANUFACTURER'S SUBMITTAL DATA WITH PERMIT
 APPLICATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT PATTY KRAUSS
 AT (561)805-6719 OR E-MAIL [email protected].