Plan Review Notes
Plan Review Notes For Permit 06090092
Permit Number 06090092
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-12 11:45:03*****DENIED*****
  
  
  
  
 1.)CONSTRUCTION, ALTERATION, ANDDEMOLITION
 OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.)DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING
 AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B.
  
 3.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL
 NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID
 PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES).
  
 4.)THE SCOPE OF THE INTERIOR BUILDOUT REQUIRING
 MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER
 SYSTEM, SEPARATE PERMIT AND PLANS ARE REQUIRED.
  
 5.)INTERIOR FINISH FOR WALLS AND CEILINGS IN EXITS
 AND EXIT CORRIDORS SHALL BE CLASS "A" OR CLASS "B".
  
 6.)ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY
 THE ADDRESS FOR THIS STRUCTURE.AS PER WEST PALM BEACH
 CODE, THE CHARACTERS (NUMBERS AND/OR LETTERS) SHALL BE
 NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH CONTRASTING
 WITH THE BACKGROUND.IF USED, HURRICANE SHUTTERS SHALL
 NOT COVER OR CONCEAL ADDRESS.
  
 7.)ADDITIONAL MECHANICAL PERMITS AND PLANS ARE
 REQUIRED FOR HOOD/SUPPRESSION SYSTEM(S).
  
 8.)ON SHEET M-3 HOOD SYSTEM NOTE #1, REFERENCES SHALL
 BE MADE TO NFPA 96, 2004 EDITION.
  
 9.)AS PER WPBFR, DUCT SMOKE DETECTORS SHALL INITIATE
 A GENERAL FIRE ALARM.
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722