2006-10-12 11:45:03 | *****DENIED***** |
| |
| |
| |
| |
| 1.)CONSTRUCTION, ALTERATION, ANDDEMOLITION |
| OPERATIONS SHALL COMPLY WITH NFPA 241. |
| |
| 2.)DEMOLITION OPERATIONS INVOLVING THE USE OF CUTTING |
| AND WELDING SHALL BE DONE IN ACCORDANCE WITH NFPA 51B. |
| |
| 3.)CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL |
| NOT INTERFERE OR HINDER EMERGENCY ACCESS TO THE SAID |
| PROPERTY OR VICINITY THEREOF (INCLUDING FIRE LANES). |
| |
| 4.)THE SCOPE OF THE INTERIOR BUILDOUT REQUIRING |
| MODIFICATION OF THE FIRE ALARM OR FIRE SPRINKLER |
| SYSTEM, SEPARATE PERMIT AND PLANS ARE REQUIRED. |
| |
| 5.)INTERIOR FINISH FOR WALLS AND CEILINGS IN EXITS |
| AND EXIT CORRIDORS SHALL BE CLASS "A" OR CLASS "B". |
| |
| 6.)ON THE APPROPIATE EXTERIOR ELEVATION, SHOW/DISPLAY |
| THE ADDRESS FOR THIS STRUCTURE.AS PER WEST PALM BEACH |
| CODE, THE CHARACTERS (NUMBERS AND/OR LETTERS) SHALL BE |
| NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH CONTRASTING |
| WITH THE BACKGROUND.IF USED, HURRICANE SHUTTERS SHALL |
| NOT COVER OR CONCEAL ADDRESS. |
| |
| 7.)ADDITIONAL MECHANICAL PERMITS AND PLANS ARE |
| REQUIRED FOR HOOD/SUPPRESSION SYSTEM(S). |
| |
| 8.)ON SHEET M-3 HOOD SYSTEM NOTE #1, REFERENCES SHALL |
| BE MADE TO NFPA 96, 2004 EDITION. |
| |
| 9.)AS PER WPBFR, DUCT SMOKE DETECTORS SHALL INITIATE |
| A GENERAL FIRE ALARM. |
| |
| |
| |
| |