Plan Review Notes
Plan Review Notes For Permit 06090092
Permit Number 06090092
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-19 00:00:00*** UNSAT ***
  
 1) NOTE: PLEASE SEE SERVICE IS BEING
 SHOWN TO A 350A CAPABILITY , HOWEVER
 RISER SHOWS A 200A METER CAN BEING
 TAPPED.
 PLEASE SEE NOTES ON LOAD CALCS, AS LOADS
 EXCEED RATINGS OF EQUIPMENT AS SHOWN.
 240.4,310.16,230.70 ETC
  
 2) NOTE: PLEASE INCLUDE CONDUCTORS FROM
 METER TO GUTTER ANF FROM GUUTER TO NEW
 MAIN.
 240.310.16 ETC
  
 3) NOTE: PLEASE SHOW LOAD ON EXISTING
 GUTEER, SIZE AND NEW LOADS BEIGN ADDED.
 220, 215. ETC.
 FBC 106.1.2 ADMIN SECT.
  
 4) NOTE: PLEASE SEE LOAD CALCS MENTIONS
 TWO PANEL "B" 'S?
 PLEASE CLARIFY.
 106.1.2 FBC.
  
 5) NOTE: PLEASE INDICATE NEW OR EXISTING
 SIGN CIRCUIT(S) PER 600.5
  
 6) NOTE: PLEASE INDICATE NEW OR EXISTIGN
 RECEPTS ABOVE WINDOWS. (EVERY 12' OR
 FRACTION THEROF.
 210.62, 220.12
  
 7) NOTE: PLEASE SEE THIS SERVICE IS
 BEING SHOWN FOR ONE TENANT, YET IT IS
 ALSO BEING SHOWN FOR FEEDING
 "COURTYARD"??
 PLEASE VERIFY AS THE CODE DOES NOT
 PERMIT COMMON AREA LIGHTING ETC BEING
 CONTROLLED OR FED FROM A TENANT
 OCCUPANCY.
 210.25, 240.24
  
 8) NOTE: PLEASE CLARIFY SHUNT BRKR FOR
 ANY HOOD POWER/ LTS. NFPA-96
  
 9) NOTE: PLEASE SEE FBC CHAPTER 13 FOR
 AUTOMATED LIGHTING CONTROLLED REQUIRED.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE PROVIDE SCHEDULING, TIMERS,
 OVER-RIDES AND TYPES OF DEVICES. PLEASE
 SHOW ALL CONTROL/OVER RIDE LOCATIONS.
 PLEASE SEE ALL SEPARATE SPACES WITH FLR
 TO CEILING HEIGHT PARTITIONS, WITH
 CONTROLS.
 PLEASE PROVIDE ENERGY CALCULATIONS AS
 REQUIRED 13-415.1.AB.1, 13-415.2.ABC.1,
 415.2.C.
  
 PLEASE SEE THERE ARE SWITCHES BEING
 SHOWN ON PLANS WHICH DO NOT INDICATE
 CONTROL OF ANY PARTICULAR ITEM.?
  
 10) NOTE: PLEASE SHOW NEW OR EXISTING
 GFI RECEPT FOR ROOF TOP EQUIPMENT PER 210.8,210.63
  
 11) NOTE: PLEASE INDICATE THE AIC
 RATINGS FOR ALL NEW SERVICE
 MAINS/EQUIPMENT.
 110.9
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  
  