Plan Review Notes
Plan Review Notes For Permit 06090011
Permit Number 06090011
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2007-04-06 15:34:34***PROVISO***
  
 1) FOR THE PURPOSE OF SATISFYING THE 100' REQUIREMENT
 OF NFPA 101, SEC. 7.10.1.5.2, IT WOULD APPEAR THAT AN
 ADDITIONAL EXIT SIGN WOULD BE REQUIRED IN THE
 WALK-OVER.
  
 2) FIRE EXTINGUISHERS TO BE MOUNTED NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION BUREAU (561) 805-4756