Plan Review Notes For Permit 06090011 |
Permit Number |
06090011 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-10-26 10:45:21 | 1. DOES THE PROPOSED PEDESTRIAN BRIDGE PLANNED TO | | PROVIDE ANY EXITING FROM THE COURTHOUSE COMMONS | | BUILDING. PLEASE PROVIDE INFORMATION. | | 2. IF EXITING IS PLANNED TO BE PROVIDED EXIT SIGNS AND | | EMERGENCY LIGHTING SHALL BE PROVIDED. | | 3. WHAT IS THE ANTICIPATED USE OF THE PEDESTRIAN | | BRIDGE. THE ANTICIPATED LOAD SHOULD BE CONSIDERED AS | | ADDITIONAL EXIT CAPACITY SOMEHWERE. | | 4. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS | | FOR ALL HANDRAILS, GAURDRAILS AND METAL PLATES. | | 5. IS THIS BRIDGE BEING CLASSIFIED AS PART OF THE | | COURTHOUSE COMMONS BUILDING OR AS AN EXTERNSION. 6. | | WHAT FIRE SAFETY FEATURES ARE PLANNED FOR THE | | PEDESTRIAN BRIDGE. | | 7. WHAT IS THE PROPOSED HEIGHT OF THE LOWEST PORTION OF | | THE BRIDGE FROM THE FINISHED GRADE OF THIRD STREET. | | FIRE RESCUE ACCESS IS REQUIRED BELOW THE BRIDGE USING | | THIRD STREET AS A ROUTE TO EMERGENCIES. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION OFFICER 804-4709 | | | | MICHAEL A. WILLIAMS, FIRE PREVENTION CAPTAIN 805-6722 |
|