Plan Review Notes
Plan Review Notes For Permit 06090011
Permit Number 06090011
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-19 00:00:00*** UNSAT ***
  
 ** PLEASE KNOW, NOT ALL NOTES BELOW
 PERTAIN TO THE TECHNICAL ELECTRICAL
 REVIEW OR APPLY TO KAMM CONSULTING
 ENGINEERS.
  
  
 1) NOTE: PLEASE SEEE NOTICE OF
 COMMENCMENT SUBMITTED HAS EXPIRED.
 PLEASE ALSO KNOW, AS THE GENERAL
 DESCRIPTION AS ORIGINALLY STATED ALSO
 DID NOT INCLUDE THE BRIDGE.
 PLEASE SEE FS 713.13(2).
 NOC'S EXOIRED AFTER ONE YEAR, EVEN IF
 JOB SITE WORK IS ON GOING.
  
 2) NOTE: PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND FS
 481.219 FOR MISSING INFORMATION REQUIRED
 ON THE TITLE BLOCKS FOR THE ARCHITECT
 AND ARCHITECTURAL FIRM.
 ** REQUIRED WHETHER COMMENT IS MADE BY
 OTHER REVIEWER(S).
  
 3) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR STRUCTURAL
 ENGINEERING FIRM AS REQUIRED UNDER FAC
 61G15-23.002, AND FS 471.023.
 MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER ALSO.
 ** REQUIRED WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
 ** PLEASE SEE SHEETS ALSO REFERENCE THE
 2001 FBC INTO DESIGN. PLEASE SEE
 BUIDLING REVIEW NOTES AS THIS PROJECT
 WAS SUBMITTED AFTER OCT 1ST, 2005 WHICH
 NOW REQUIRES THE DESIGNS, CODES STATE AS
 THE 2004 FBC.
 ** NOT AN ELECTRICAL COMMENT, ONLY GIVEN
 FOR INFORMATIONAL PURPOSE.
  
 4) NOTE: PLEASE PROVIDE A NOTE ON THE
 ELECTRICAL E-1 AS EACH ELECTRICAL BOX ON
 THE BRIDGE SHALL CONTAIN LABLELING FOR
 WHERE THE CIRCUIT IS BEING FED FROM.
  
 5) NOTE: PLEASE PROVIDE CURRENT AND
 RELEVANT CODES/ EDITIONS ON PLANS.
 2002 NFPA-70, 2003 NFPA-101, 2002
 NFPA-72 ETC.
  
 6) NOTE: PLEASE PROVIDE BONDING OF NEW
 STEEL/STRUCTURE TO THE ELECTRICAL SYSTEM
 OF THE EXISTING BUILDING WHICH IS
 PROVIDING POWER FOR LIGHTING TO NEW
 WALKWAY.
 250.50, 250.104
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  