Date |
Text |
2006-09-19 00:00:00 | *** UNSAT *** |
| |
| ** PLEASE KNOW, NOT ALL NOTES BELOW |
| PERTAIN TO THE TECHNICAL ELECTRICAL |
| REVIEW OR APPLY TO KAMM CONSULTING |
| ENGINEERS. |
| |
| |
| 1) NOTE: PLEASE SEEE NOTICE OF |
| COMMENCMENT SUBMITTED HAS EXPIRED. |
| PLEASE ALSO KNOW, AS THE GENERAL |
| DESCRIPTION AS ORIGINALLY STATED ALSO |
| DID NOT INCLUDE THE BRIDGE. |
| PLEASE SEE FS 713.13(2). |
| NOC'S EXOIRED AFTER ONE YEAR, EVEN IF |
| JOB SITE WORK IS ON GOING. |
| |
| 2) NOTE: PLEASE SEE FLORIDA |
| ADMINISTRATIVE CODE 61G1-16.004 AND FS |
| 481.219 FOR MISSING INFORMATION REQUIRED |
| ON THE TITLE BLOCKS FOR THE ARCHITECT |
| AND ARCHITECTURAL FIRM. |
| ** REQUIRED WHETHER COMMENT IS MADE BY |
| OTHER REVIEWER(S). |
| |
| 3) NOTE: PLEASE SEE MISSING INFORMATION |
| ON TITLE BLOCKS FOR STRUCTURAL |
| ENGINEERING FIRM AS REQUIRED UNDER FAC |
| 61G15-23.002, AND FS 471.023. |
| MISSING CERTIFICATE OF AUTHORIZATION |
| NUMBER ALSO. |
| ** REQUIRED WHETHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| ** PLEASE SEE SHEETS ALSO REFERENCE THE |
| 2001 FBC INTO DESIGN. PLEASE SEE |
| BUIDLING REVIEW NOTES AS THIS PROJECT |
| WAS SUBMITTED AFTER OCT 1ST, 2005 WHICH |
| NOW REQUIRES THE DESIGNS, CODES STATE AS |
| THE 2004 FBC. |
| ** NOT AN ELECTRICAL COMMENT, ONLY GIVEN |
| FOR INFORMATIONAL PURPOSE. |
| |
| 4) NOTE: PLEASE PROVIDE A NOTE ON THE |
| ELECTRICAL E-1 AS EACH ELECTRICAL BOX ON |
| THE BRIDGE SHALL CONTAIN LABLELING FOR |
| WHERE THE CIRCUIT IS BEING FED FROM. |
| |
| 5) NOTE: PLEASE PROVIDE CURRENT AND |
| RELEVANT CODES/ EDITIONS ON PLANS. |
| 2002 NFPA-70, 2003 NFPA-101, 2002 |
| NFPA-72 ETC. |
| |
| 6) NOTE: PLEASE PROVIDE BONDING OF NEW |
| STEEL/STRUCTURE TO THE ELECTRICAL SYSTEM |
| OF THE EXISTING BUILDING WHICH IS |
| PROVIDING POWER FOR LIGHTING TO NEW |
| WALKWAY. |
| 250.50, 250.104 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
| |