2006-10-04 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 06090011 |
| ADD: 444 W. RAILROAD AVE. |
| CONT:PBM DEVELOPMENT |
| TEL: (561)368-2544 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF |
| COMMENCEMENT IS NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| THE ORIGINAL NOTICE OF COMMENCEMENT |
| IS OVER ONE YEAR OLD , NO LONGER VALID. |
| |
| 3) STRUCTURAL SHEETS: THE ENGINEER OF |
| RECORDS FIRM IS MISSING THEIR |
| CERTIFICATE OF AUTHORIZATIN. 471.023 |
| F.S. / 61G1-16.004 FL ADMINISTRATIVE |
| CODE.CERTIFICATE OF AUTHORIZATION. |
| THE TITLE BLOCK FOR ANY SHEET BEARING |
| THE NAME OF AN ENGINEER PRACTICING UNDER |
| A FICTITIOUS NAME, A CORPORATION, OR A |
| PARTNERSHIP, OFFERING ENGINEERING |
| SERVICES, SHALL INCLUDE THE CERTIFICATE |
| OF AUTHORIZATION NUMBER. |
| ADD THE NUMBER TO EACH SHEET.THIS MAY |
| BE ADDED BY HAND. |
| |
| 4) PLEASE RECORD THE PEDESTRIAN WALKWAY |
| EASEMENT AGREEMENT WITH THE COUNTY |
| CLEARK OF THE COURT. |
| |
| 5)THE ARCHITECTURAL SHEETS DO NOT |
| PROVIDE THE FOLLOWING INFORMATION: |
| 110.2* W. P. B. ADMINISTRATIVE CODE, |
| INFORMATION THAT IS REQUIRED FOR RECORD |
| KEEPING & FOR CERTIFICATE OF OCCUPANCY: |
| A) THE EDITION OFTHE CODE UNDER WHICH |
| THE PERMIT WAS ISSUED. |
| B) THE USE AND OCCUPANCY, IN ACCORDANCE |
| WITH THE PROVISIONS OF CHAPTER 3. |
| C) THE TYPE OF CONSTRUCTION AS DEFINED |
| IN CHAPTER 6, TABLE 601. |
| D) THE OCCUPANT LOAD, SEE 1004. |
| E) IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| PROVIDED? |
| F) WHETHER THE SPRINKLER SYSTEM IS |
| REQUIRED. |
| F) ANY SPECIAL STIPULATIONS & CONDITIONS |
| OF THE BUILDING PERMIT. |
| |
| 6) A100.04 INDICATES THE PEDESTRIAN |
| BRIDE HAS A LENGTH OF 142'. PLEASE |
| PROVIDE A LIFE SAFETY PLAN FOR THE |
| PEDESTRIAN BRIDGE PROVIDING THE TRAVEL |
| DISTANCE TO THE VERTICAL EXITS FOR BOTH |
| BUILDINGS. 3104.9 THE LENGTH OF EXIT |
| ACCESS SHALL NOT EXCEED 200 FT. ALSO SEE |
| EXECEPTIONS. |
| |
| 7) SHEET A100.05 SECTION B-B INDICATES A |
| SECTION THROUGH THE COVERED PEDESTRIAN |
| BRIDGE. PLANS DO NOT PROVIVE THE |
| DIMENSION OF THE HANDRAIL NOR THE CLEAR |
| SPACE BETWEEN THE MESH AND HANDRAIL. |
| 11-4.8.5(3). |
| |
| 8) THIS SAME SECTIONINDICATES THE USE |
| OF A METAL ROOF SYSTEM, PLEASE PROVIDE |
| ADDITIONAL INFORMATION. PLANS ARE NOT |
| CLEAR IF THIS IS A STRUCTURAL METAL ROOF |
| SYSTEM OR METAL ROOF PANELS (1507.4) |
| REQUIRINGA SOLID CLOSE FITTING DECK. |
| 106.1.2* ADDITIONAL INFO REQUIRED. |
| |
| 9) SHEET S).1 PLEASE CORRECT THE |
| REFRENCES TO THE 2001 FBC. |
| |
| 10) S0.1 & S2.1 BOTH INDICATE THE USE OF |
| AUGER PILE FOR THE PEDESTRIAN BRIDGE. |
| PLEASE SUBMIT GEOTECH REPORT THAT |
| PROVIDES THE LOADING OR LENGTH OF THE |
| AUGER PILE, NOT STATED ON PLANS. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |
| |
| |
| |
| |
| |
| |
| |