Plan Review Notes
Plan Review Notes For Permit 06082250
Permit Number 06082250
Review Stop B
Sequence Number 1
Notes
Date Text
2006-09-18 00:00:00 
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
  
 1) 2004 FL. BLD CODE 1603.1.4 THE
 FOLLOWING INFORMATION RELATED TO WIND
 SHALL BE SHOWN ON THE CONSTRUCTION
 DRAWINGS,
 1)- BASIC WIND SPEED, MPH
 2)- WIND IMPORTANCE FACTOR, & BUILDING
 CATEGORY
 3)- WIND EXPOSURE
 4)- INTERNAL PRESSURE COEFFICIENT,
 5)- COMPONENTS & CLADDING, THE DESIGN
 WIND PRESSURES IN TERMS OF PSF.
  
 2) THE DETAIL SHEETS ARE MISSING FROM
 THE PACKAGE. SUBMIT THE DETAIL SHEETS
 WHICH SHOW THE CONNECTION DETAILS OF THE
 NEW FLEX AWNINGS AND THE NEW BULLNOSE.
  
 3)THE COVER SHEET HAS A DRAWING INDEX,
 HOWEVER, SOME THE SHEETS MENTIONED ON
 THE DRAWING INDEX WERE NOT SUBMITTED.
 ALL THOSE SHEETS MENTIONED ON THE COVER
 NEEDS TO BE SUBMITTED WITH THIS PACKAGE
 OR REMOVE THAT INDEX SHEET.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER