2007-01-09 11:22:34 | DENIED 2ND TIME |
| REFERENCE: FBC-2001 PLUMBING |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| PLAN REVIEW ON THE RESUBMITTED SHEET P2 SANITARY RISER |
| DIAGRAM TO MEET CODE COMPLIANCE: |
| |
| 1.SHEET P2 FIRST FLOOR UNIT #1: A} VENT REQUIRED FOR |
| DOUBLE BOWL SINK W/DISHWASHER PER FBC-2001 PLUMBING, |
| SEC. 901.2.1 B} PLEASE INDICATE DOUBLE BOWL SINK |
| W/DISHWASHER AND ADD DRAIN FOR DISHWASHER PER FBC-2001 |
| SEC. 409.3.1. |
| |
| 2.SHEET P2 FIRST FLOOR UNIT #2: A} VENT REQUIRED FOR |
| DOUBLE BOWL SINK W/DISHWASHER PER FBC-2001 PLUMBING, |
| SEC. 901.2.1. B} PLEASE INDICATE DOUBLE BOWL SINK |
| W/DISHWASHER AND ADD DRAIN FOR DISHWASHER PER FBC-2001 |
| PLUMBING SEC. 409.3.1. |
| |
| 3. SHEET P2 SECOND FLOOR UNIT #3: A} VENT REQUIRED FOR |
| BATHROOM GROUP PER FBC-2001 PLUMBING SEC. 909.1. B} |
| PLEASE INDICATE DOUBLE BOWL SINK W/ DISHWASHER AND ADD |
| DRAIN FOR DISHWASHER PER FBC-2001 PLUMBING SEC. |
| 409.3.1. |
| |
| 4. SHEET P2 GARAGE WASHING MACHINE: A} PLEASE INDICATE |
| STANDPIPE FOR WASHING MACHINE DRAIN PER FBC-2001 |
| PLUMBING, SEC. 802.4. B} PLEASE INDICATE CLEANOUT FOR |
| WASHING MACHINE AT FOUR FEET ABOVE FINNISH FLOOR (4' |
| A.F.F.) PER FBC-2001 PLUMBING SEC. 708.10. |
| |
| **********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |