2007-01-09 11:22:34DENIED 2ND TIME
 REFERENCE: FBC-2001 PLUMBING
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW ON THE RESUBMITTED SHEET P2 SANITARY RISER
 DIAGRAM TO MEET CODE COMPLIANCE:
  
 1.SHEET P2 FIRST FLOOR UNIT #1: A} VENT REQUIRED FOR
 DOUBLE BOWL SINK W/DISHWASHER PER FBC-2001 PLUMBING,
 SEC. 901.2.1 B} PLEASE INDICATE DOUBLE BOWL SINK
 W/DISHWASHER AND ADD DRAIN FOR DISHWASHER PER FBC-2001
 SEC. 409.3.1.
  
 2.SHEET P2 FIRST FLOOR UNIT #2: A} VENT REQUIRED FOR
 DOUBLE BOWL SINK W/DISHWASHER PER FBC-2001 PLUMBING,
 SEC. 901.2.1. B} PLEASE INDICATE DOUBLE BOWL SINK
 W/DISHWASHER AND ADD DRAIN FOR DISHWASHER PER FBC-2001
 PLUMBING SEC. 409.3.1.
  
 3. SHEET P2 SECOND FLOOR UNIT #3: A} VENT REQUIRED FOR
 BATHROOM GROUP PER FBC-2001 PLUMBING SEC. 909.1. B}
 PLEASE INDICATE DOUBLE BOWL SINK W/ DISHWASHER AND ADD
 DRAIN FOR DISHWASHER PER FBC-2001 PLUMBING SEC.
 409.3.1.
  
 4. SHEET P2 GARAGE WASHING MACHINE: A} PLEASE INDICATE
 STANDPIPE FOR WASHING MACHINE DRAIN PER FBC-2001
 PLUMBING, SEC. 802.4. B} PLEASE INDICATE CLEANOUT FOR
 WASHING MACHINE AT FOUR FEET ABOVE FINNISH FLOOR (4'
 A.F.F.) PER FBC-2001 PLUMBING SEC. 708.10.
  
 **********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  