Date |
Text |
2006-10-02 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 PLUMBING |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLUMBING PLAN REVIEW. PLEASE |
| REFERENCE THE CORRECTED DRAWINGS IN RED |
| INK FOR RESUBMITTAL: |
| |
| 1. PLEASE CHANGE THE WORDING ON SHEET |
| P-1, COPPER PIPE SCH. 40 TO READ, COPPER |
| PIPE TYPE "L" FOR THE RESUBMITTAL. |
| 2. PER FBC-2004 SEC. 608.15.4.2 HOSE |
| CONNECTIONS: PLEASE CHANGE THE WORDING |
| ON SHEET P-1, PLUMBING NOTE #4 TO READ |
| VACUUM BREAKERS INSTEAD OF BACKFLOW |
| PREVENTERS. |
| 3. THE S.V.= STUDOR VENTS (AUTOMATIC AIR |
| VENTS) INDICATED ON SHEET P-2 ARE NOT |
| REQUIRED BECAUSE THE SANITARY ISOMETRIC |
| PLUMBING RISER DIAGRAM INDICATES V.T.R. |
| (VENTS THROUGH ROOF). PLEASE DELETE THE |
| S.V. FOR THE RESUBMITTAL. |
| 4. PER FBC-2004, PLUMBING, SECTION 909.1 |
| WET VENT PERMITTED: ONLY THE FIXTURES |
| WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| TO THE WET-VENTED HORIZONTAL BRANCH |
| DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| DISCHARGE DOWNSTREAM OF THE WET VENT. |
| NOTE: THE KITCHEN SINK INDICATED ON |
| SHEET P-2 SANITARY RISER DIAGRAM FOR |
| UNIT #2 IS PIPED WRONG, PLEASE REFERENCE |
| THE CORRECTED DRAWING IN RED INK FOR |
| RESUBMITTAL. |
| 5. PER FBC-2004 PLUMBING, SECTION 1002.1 |
| A FIXTURE SHALL NOT BE DOUBLE TRAPPED. |
| NOTE: THE W.C. INDICATED ON SHEET P-2 |
| SANITARY RISER DIAGRAM HAS AN INTREGRAL |
| TRAP THEREFORE A TRAP NEED NOT BE |
| INDICATED FOR THE W.C. ON THE SANITARY |
| RISER DIAGRAM. PLEASE CORRECT FOR THE |
| RESUBMITTAL. |
| 6. PER FBC-2004 PLUMBING TABLE 403.1 |
| MINIMUM NUMBER OF REQUIRED FIXTURES: |
| ONE (1) AUTOMATIC CLOTHES WASHER |
| REQUIRED PER TWENTY (20) DWELLING UNITS. |
| PLEASE INDICATE ON THE RESUBMITTAL THE |
| AUTOMATIC CLOTHES WASHER LOCATION. |
| 7. PER FBC-2004 PLUMBING, SECTION |
| 901.2.1 VENTING REQUIRED: THE TUBS |
| INDICATED ON SHEET P-2, UNITS #1 AND #2 |
| REQUIRE VENTS. |
| 8. PLEASE INDICATE ON THE RESUBMITTAL IF |
| THERE IS ANY PLUMBING IN THE EXISTING |
| GARAGE. IF THERE IS PLUMBING IN THE |
| GARAGE PLEASE INDICATE PLUMBING ON THE |
| SANITARY ISOMETRIC RISER DIAGRAM. |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |
| |
| |