Plan Review Notes
Plan Review Notes For Permit 06082241
Permit Number 06082241
Review Stop P
Sequence Number 1
Notes
Date Text
2006-10-02 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW. PLEASE
 REFERENCE THE CORRECTED DRAWINGS IN RED
 INK FOR RESUBMITTAL:
  
 1. PLEASE CHANGE THE WORDING ON SHEET
 P-1, COPPER PIPE SCH. 40 TO READ, COPPER
 PIPE TYPE "L" FOR THE RESUBMITTAL.
 2. PER FBC-2004 SEC. 608.15.4.2 HOSE
 CONNECTIONS: PLEASE CHANGE THE WORDING
 ON SHEET P-1, PLUMBING NOTE #4 TO READ
 VACUUM BREAKERS INSTEAD OF BACKFLOW
 PREVENTERS.
 3. THE S.V.= STUDOR VENTS (AUTOMATIC AIR
 VENTS) INDICATED ON SHEET P-2 ARE NOT
 REQUIRED BECAUSE THE SANITARY ISOMETRIC
 PLUMBING RISER DIAGRAM INDICATES V.T.R.
 (VENTS THROUGH ROOF). PLEASE DELETE THE
 S.V. FOR THE RESUBMITTAL.
 4. PER FBC-2004, PLUMBING, SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
 NOTE: THE KITCHEN SINK INDICATED ON
 SHEET P-2 SANITARY RISER DIAGRAM FOR
 UNIT #2 IS PIPED WRONG, PLEASE REFERENCE
 THE CORRECTED DRAWING IN RED INK FOR
 RESUBMITTAL.
 5. PER FBC-2004 PLUMBING, SECTION 1002.1
 A FIXTURE SHALL NOT BE DOUBLE TRAPPED.
 NOTE: THE W.C. INDICATED ON SHEET P-2
 SANITARY RISER DIAGRAM HAS AN INTREGRAL
 TRAP THEREFORE A TRAP NEED NOT BE
 INDICATED FOR THE W.C. ON THE SANITARY
 RISER DIAGRAM. PLEASE CORRECT FOR THE
 RESUBMITTAL.
 6. PER FBC-2004 PLUMBING TABLE 403.1
 MINIMUM NUMBER OF REQUIRED FIXTURES:
 ONE (1) AUTOMATIC CLOTHES WASHER
 REQUIRED PER TWENTY (20) DWELLING UNITS.
 PLEASE INDICATE ON THE RESUBMITTAL THE
 AUTOMATIC CLOTHES WASHER LOCATION.
 7. PER FBC-2004 PLUMBING, SECTION
 901.2.1 VENTING REQUIRED: THE TUBS
 INDICATED ON SHEET P-2, UNITS #1 AND #2
 REQUIRE VENTS.
 8. PLEASE INDICATE ON THE RESUBMITTAL IF
 THERE IS ANY PLUMBING IN THE EXISTING
 GARAGE. IF THERE IS PLUMBING IN THE
 GARAGE PLEASE INDICATE PLUMBING ON THE
 SANITARY ISOMETRIC RISER DIAGRAM.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved