2006-09-18 00:00:00 | |
| |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} THE 3/0 SERVICE CONDUCTORS ARE NOT |
| LARGE ENOUGH FOR THE CALCULATED LOAD. |
| SEE 310.15(B)(6). |
| |
| 2} THERE IS NO WATER HEATER LISTED IN |
| THE HOUSE PANEL, YET THE REQUIRED |
| LAUNDRY CIRCUIT (WASHER) IS LISTED IN |
| THAT PANEL. PLEASE VERIFY THERE IS NO |
| HOT WATER TO BE SUPPLIED TO THE WASHER. |
| THE GARAGE PLUMBING DOES NOT SEEM TO BE |
| ON THE PLUMBING RISR. |
| |
| 3} THE BREAKFAST ROOM LISTED ON THE |
| PANEL SCHEDULES,PANELS 1, 2, AND 3 MUST |
| BE ON A 20AMP CIRCUIT PER 210.52(B)(1). |
| |
| 4} THE BATH CIRCUITS SHALL BE 20 AMP. |
| 210.11(C)(3). |
| |
| 5} PLEASE SEE ALL KITCHEN RECEPTACLES |
| MUST COMPLY WITH 210.52(B). TWO |
| RECEPTACLES IN UNIT #1, ONE LISTED ON |
| C13 AND THE OTHER NOT LISTED BUT ON WITH |
| A LIVING ROOM OUTLET, DO NOT COMPLY. |
| |
| 6} THE BREAKFAST ROOM CIRCUIT IN UNIT #2 |
| MAY NOT FEED THE LIVING ROOM OUTLETS. |
| 210.52(B)(2). |
| |
| 7} UNIT #3 KITCHEN NEEDS A RECEPTACLE |
| ADDED BY THE RANGE TO COMPLY WITH |
| 210.52(C)(1). |
| |
| 8} THE SMOKE DETECTOR LOCATION OUTSIDE |
| THE BEDROOMS DO NOT COMPLY WITH THE |
| "IMMEDIATE VICINITY" INTENT OF R313.1.1 |
| 2. |
| |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |