Plan Review Notes
Plan Review Notes For Permit 06082241
Permit Number 06082241
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-18 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE 3/0 SERVICE CONDUCTORS ARE NOT
 LARGE ENOUGH FOR THE CALCULATED LOAD.
 SEE 310.15(B)(6).
  
 2} THERE IS NO WATER HEATER LISTED IN
 THE HOUSE PANEL, YET THE REQUIRED
 LAUNDRY CIRCUIT (WASHER) IS LISTED IN
 THAT PANEL. PLEASE VERIFY THERE IS NO
 HOT WATER TO BE SUPPLIED TO THE WASHER.
 THE GARAGE PLUMBING DOES NOT SEEM TO BE
 ON THE PLUMBING RISR.
  
 3} THE BREAKFAST ROOM LISTED ON THE
 PANEL SCHEDULES,PANELS 1, 2, AND 3 MUST
 BE ON A 20AMP CIRCUIT PER 210.52(B)(1).
  
 4} THE BATH CIRCUITS SHALL BE 20 AMP.
 210.11(C)(3).
  
 5} PLEASE SEE ALL KITCHEN RECEPTACLES
 MUST COMPLY WITH 210.52(B). TWO
 RECEPTACLES IN UNIT #1, ONE LISTED ON
 C13 AND THE OTHER NOT LISTED BUT ON WITH
 A LIVING ROOM OUTLET, DO NOT COMPLY.
  
 6} THE BREAKFAST ROOM CIRCUIT IN UNIT #2
 MAY NOT FEED THE LIVING ROOM OUTLETS.
 210.52(B)(2).
  
 7} UNIT #3 KITCHEN NEEDS A RECEPTACLE
 ADDED BY THE RANGE TO COMPLY WITH
 210.52(C)(1).
  
 8} THE SMOKE DETECTOR LOCATION OUTSIDE
 THE BEDROOMS DO NOT COMPLY WITH THE
 "IMMEDIATE VICINITY" INTENT OF R313.1.1
 2.
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  