Plan Review Notes For Permit 06082221 |
Permit Number |
06082221 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-01-10 12:48:59 | ** NOTES REDLINED ** | | | | 1) LOCATION OF FIRE PUMP TO BE IN A RATED ROOM AND | | LOCATION WAS APPROVED BY THE FIRE MARSHAL'S OFFICE. | | LOCATION OFKNOX-BOX FOR ACCESS TO BE DETERMINED BY | | THE FIRE MARSHAL'S OFFICE AND MUST BE IN PLACE BEFORE | | ANY FINAL ELECTRICAL INSPECTION. LOCATION/INSTALLATION | | OF THIS EXISTING FIRE PUMP/CONTROLLER LOCATION IS NOT | | PER ELECTRICAL PLAN REVIEW. | | | | 2) LOCATION OF EXISTING SERVICE MAINS AND METERS SHALL | | CONTAIN SIGNAGE DENOTING THE LOCATION OF THE FIRE | | PUMP/FIRE PUMP CONTROLLER FOR THE DISCONNECTING MEANS | | AND HOW TO OBTAIN ACCESS ETC. | | SIGNAGE SHALL CONTAIN LETTERING OF A MINIMUM OF 1INCH | | IN HEIGHT WITH A CONTRASTING BACKGROUND. SIGNAGE SHALL | | BE PERMANENTLY ATTACHED TO THE BUILDING/STRUCTURE AND | | SHALL BE COMPLETELY RESISTANT TO FADING AS THIS IS | | LOCATED OUTSIDE. | | 230.2E | | | | | | IF THERE ARE NAY QUESTIONS, PLEASE DO NOT HESITATE IN | | CONTACTING THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLANS EXAMINER | | 561-805-6717 | | [email protected] |
|