Plan Review Notes For Permit 06082221 |
Permit Number |
06082221 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-12-08 08:40:37 | DENIED; | | 1.A DRINKING FOUNTAIN IS REQUIRED NOT A WATER COOLER. A | | DRAIN IS REQUIRED, PLEASE SHOW ON SANITARY RISER | | DIAGRAM. SEE SECTION 410.1 | | 2. DRINKING FOUNTAIN TO MEET ACCESSIBILITY CODES | | SECTION 11-4.1.3(10)A HI-LOW FOUNTAIN OR ONE D/F SET | | AT HANDICAP HIGHT WITH A CUP DISPENSOR. SHOW A DETAIL | | OF DRINKING FOUNTAIN WITH ALL MEASURMENTS REQUIRED BY | | SECTIONS 11-4.15.1 THRU 11-4.15.5. | | PLUMBING PLAN REVIEW; | | JOHN LEECH | | 805-6695 |
|