2006-11-17 10:59:54 | ** UNSAT 2ND REVIEW ** |
| |
| ** PLEASE SEE THERE ARE MOSTLY NEW COMMENTS BASED ON |
| THE REVISED RISER DIAGRAM SUBMITTED. |
| |
| |
| 1NOTE: PLEASE SEE RISER NOW INDICATES THE NEW "TENANT |
| SPACE" SERVICE BEING FROM THE BUILDINGS MAIN ELECTRICAL |
| SERVICE, HOWEVER PLEASE PROVIDE THE SIZE OF THE |
| EXISTING MAIN ELECTRICAL SERVICE AND THE LOAD ON SUCH |
| SERVICE WITH THE NEW TENANTS SERVICE LOAD BEING ADDED |
| TO IT. |
| NEC 220 |
| FBC106.3.5.1.2 ADMIN SECT. |
| |
| 2) NOTE: PLEASE SUBMIT AND PROVIDE AIC RATINGS FOR NEW |
| SERVICE EQUIPMENT. PLEASE SEE 110.9 AND 240.12 FOR |
| SELECTIVE COORDINATION. |
| |
| 3) NOTE: PLEASE SEE FIRE PUMP ROOM FOR EXISTING FIRE |
| PUMP IS BEING SHOWN IN A NEW PROPOSED TENANT SPACE. |
| PLEASE KNOW, AS THIS BUILDING DOES NOT SEEM TO MEET THE |
| EXCEPTIONS IN THE CODE UNDER NFPA-20 (FIRE |
| PUMPS)(CHAPTERS 6-3, AND ALSO CHAPER 7) AND NEC 695, |
| 230.70, 230.2, , PLEASE KNOW THE ACCESS TO THE FIRE |
| PUMP AND ANY FIRE PUMP CONTROLLER MUST BE FROM A COMMON |
| AREA/CORRIDOR OR OUTSIDE. ACCESS THROUGH ONES TENANTS |
| SPACE IS NOT PERMITTED. |
| |
| |
| 4) NOTE: PLEASE SEE METHOD "A" IS BEING SUBMITTED FOR |
| THIS NEW SPACE HOWEVER THE METHOD "A" DOES NOT SEEM TO |
| CORRELATE WITH SCOPE OF. PLEASE SEE OTHER METHODS. "B". |
| 13-415.2 |
| PLEASE ALSO SEE THAT THE CALCULATIONS AS SUBMITTED |
| INDICATE MANUAL CONTROLS, HOWEVER AUTOMATED CONTROLS |
| ARE SHOWN ON PLANS? |
| PLEASE ALSO SEE THAT THE ENERGY CALCULATIONS ARE |
| REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGNER |
| OF RECORD. |
| 13-415.1.AB.1, 13-415.2.ABC.1 |
| |
| 5) NOTE: PLEASE SE RISER AS SHOWN DOES NOT SEEM TO |
| INDICATE ANY "MAIN" ON THE LINE SIDE OF THE GUTTER, |
| THEREFORE AND EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT |
| BE INSTALLED TO THE METER FROM THE GUTTER. IF A MAIN |
| DOES EXISTS ON THE LINE SIDE OF THE GUTTER THEN ONE |
| WOULD BE INSTALLED HOWEVER THE NEW TENANT METER WOULD |
| THEN CONTAIN NOTES FOR A FLOATING NEUTRAL KIT. |
| PLEASE SEE 250.6, 250.24B. |
| |
| |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF |
| THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE |
| DO NOT HESITATEIN CONTACTING THIS REVIEWER. |
| |
| |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |