2006-11-17 10:59:54** UNSAT 2ND REVIEW **
  
 ** PLEASE SEE THERE ARE MOSTLY NEW COMMENTS BASED ON
 THE REVISED RISER DIAGRAM SUBMITTED.
  
  
 1NOTE: PLEASE SEE RISER NOW INDICATES THE NEW "TENANT
 SPACE" SERVICE BEING FROM THE BUILDINGS MAIN ELECTRICAL
 SERVICE, HOWEVER PLEASE PROVIDE THE SIZE OF THE
 EXISTING MAIN ELECTRICAL SERVICE AND THE LOAD ON SUCH
 SERVICE WITH THE NEW TENANTS SERVICE LOAD BEING ADDED
 TO IT.
 NEC 220
 FBC106.3.5.1.2 ADMIN SECT.
  
 2) NOTE: PLEASE SUBMIT AND PROVIDE AIC RATINGS FOR NEW
 SERVICE EQUIPMENT. PLEASE SEE 110.9 AND 240.12 FOR
 SELECTIVE COORDINATION.
  
 3) NOTE: PLEASE SEE FIRE PUMP ROOM FOR EXISTING FIRE
 PUMP IS BEING SHOWN IN A NEW PROPOSED TENANT SPACE.
 PLEASE KNOW, AS THIS BUILDING DOES NOT SEEM TO MEET THE
 EXCEPTIONS IN THE CODE UNDER NFPA-20 (FIRE
 PUMPS)(CHAPTERS 6-3, AND ALSO CHAPER 7) AND NEC 695,
 230.70, 230.2, , PLEASE KNOW THE ACCESS TO THE FIRE
 PUMP AND ANY FIRE PUMP CONTROLLER MUST BE FROM A COMMON
 AREA/CORRIDOR OR OUTSIDE. ACCESS THROUGH ONES TENANTS
 SPACE IS NOT PERMITTED.
  
  
 4) NOTE: PLEASE SEE METHOD "A" IS BEING SUBMITTED FOR
 THIS NEW SPACE HOWEVER THE METHOD "A" DOES NOT SEEM TO
 CORRELATE WITH SCOPE OF. PLEASE SEE OTHER METHODS. "B".
 13-415.2
 PLEASE ALSO SEE THAT THE CALCULATIONS AS SUBMITTED
 INDICATE MANUAL CONTROLS, HOWEVER AUTOMATED CONTROLS
 ARE SHOWN ON PLANS?
 PLEASE ALSO SEE THAT THE ENERGY CALCULATIONS ARE
 REQUIRED TO BE SIGNED, DATED AND SEALED BY THE DESIGNER
 OF RECORD.
 13-415.1.AB.1, 13-415.2.ABC.1
  
 5) NOTE: PLEASE SE RISER AS SHOWN DOES NOT SEEM TO
 INDICATE ANY "MAIN" ON THE LINE SIDE OF THE GUTTER,
 THEREFORE AND EQUIPMENT GROUNDING CONDUCTOR SHOULD NOT
 BE INSTALLED TO THE METER FROM THE GUTTER. IF A MAIN
 DOES EXISTS ON THE LINE SIDE OF THE GUTTER THEN ONE
 WOULD BE INSTALLED HOWEVER THE NEW TENANT METER WOULD
 THEN CONTAIN NOTES FOR A FLOATING NEUTRAL KIT.
 PLEASE SEE 250.6, 250.24B.
  
  
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved