2006-11-22 13:51:00 | PERMIT: 06082221 |
| ADD: 500 PALM ST SUITE "C" |
| CONT: MIKE MOORE CONST |
| TEL: (561)748-7000 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3 2ND REQUEST #8 FROM THE PREVIOUS REVIEW, |
| FL BLD CODE 1609.1.4 : COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| B) ROOFING ASSEMBLIES |
| THE ROOF REPORT SUBMITTED DOESN'T HAVE THE FLORIDA |
| COVERSHEET |
| NOR ARE THE SUBSYSTEM REPORTSHIGHLIGHTED AS TO WHICH |
| |
| SUBSYSTEM IS BEING USED. NOTE OVER 1/2 OF THE SUBSYSTEM |
| REPORTS ARE FOR |
| INSULATED ROOFS. OTHER SUBSYSTEM REPORTS ARE TO BE USED |
| ONLY AS AN TILE |
| UNDERLAYMENT. PLEASE NOTE MOST OF THE SUBSYSTEM REPORTS |
| ONLY HAVE A |
| MAXIMUM DESIGN PRESSURE OF -45 TO -60 WITH A LIMITATION |
| # 7, NO |
| ENHANCED FASTENING!!!!PLEASE HAVE THE DESIGN |
| PROFESSIONALS REVIEW |
| FOR CODE COMPLIANCE BEFORE SUBMITTAL TO THE CITY |
| !!!!!!!!!!!!!!!!!!!! |
| |
| 9) W P B ADMINISTRTIVE CODE 106.3.3* |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |