Plan Review Notes
Plan Review Notes For Permit 06082221
Permit Number 06082221
Review Stop P
Sequence Number 1
Notes
Date Text
2006-09-07 00:00:00DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 11
  
 1. PER TABLE 403.1 AND SECTION 410.1 A
 DRINKING FOUNTAIN IS REQUIRED. SHOW
 CONNECTION TO SANT. AND WATER RISER
 DIAGRAMS.
  
 2. SUBMIT A WATER RISER DIAGRAM SHOWING
 ALL PIPE SIZES, VALVES ETC. SECTIONS
 106.3.5.1.3 AND 606.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731