2006-09-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06082221
 ADD: 500 PALM ST SUITE "C"
 CONT: MIKE MOORE CONST
 TEL: (561)748-7000
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SHEET A2.1 THE RESTROOM DOOR IS
 MISSING THE 18" CLEAR SPACE LATCH SIDE
 OF DOOR.11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 4) EXISTING BUILDING CODE LEVEL 2
 ALTERATION: 611.1 MINIMUM REQUIREMENTS: ALTERATIONS
 SUBJECT TO THIS CHAPTER
 SHALL COMPLY WITH THE REQUIREMENTS OF
 CHAPTER 13 OF THE FLORIDA BUILDING CODE
 BUILDING.
 13-101.1.3 RENOVATIONS.
 RENOVATED COMMERCIAL BUILDINGS SHALL,
 WHEN APPLICABLE (SEE SECTION 202 ),
 COMPLY WITH THE PRESCRIPTIVE
 REQUIREMENTS CONTAINED IN FORM 400 C OR
 WITH METHOD B OF SUBCHAPTER 13-4 FOR
 INSULATION, HVAC SYSTEMS, LIGHTING,
 WATER HEATING SYSTEMS AND EXTERIOR
 ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED.
  
 5)ENGINEER GLENN GOLDBERG SEAL USING THE
 PHRASE "CERTIFICATE"
 RULE 61G155-23.001(1) F.A.C.
 THE FLORIDA BOARD OF PROFESSIONAL
 ENGINEERS HAS CLEANED UP THE APPEARANCE
 OF THE SEAL BY ELIMINATING OBSOLETE
 CONTENT AND CHANGING THE WORD
 "CERTIFICATE" TO "LICENSE". A GRACE
 PERIOD RAN THROUGH DEC. 31,2005.
  
 6) ENGINEER GLENN GOLDBERG:
 61G15-23.002(2)FL. ADMIN. CODE. PLANS
 SIGNED & SEALED BY A PROFESSIONAL
 ENGINEER SHALL INCLUDE EITHER THE NAME,
 ADDRESS AND LICENSE NUMBER OF THE
 ENGINEER OR, THE NAME AND LICENSE NUMBER
 OF THE ENGINEER AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH
 WHICH THE ENGINEER IS PRACTICING
 (471.025 F.S. AND 471.023 F.S.).
  
 7) VINTAGE DESIGN AND CONSTRUCTION
 STRUCTURAL ENGINEER CONSULTANT:
 471.023 F.S.CERTIFICATE OF
 AUTHORIZATION.THE TITLE BLOCK FOR ANY
 SHEET BEARING THE NAME OF AN ENGINEER
 PRACTICING UNDER A FICTITIOUS NAME, A
 CORPORATION, OR A PARTNERSHIP, OFFERING ENGINEERING
 SERVICES, SHALL INCLUDE THE CERTIFICATE OF
 AUTHORIZATION NUMBER.
 ADD THE NUMBER TO EACH SHEET.THIS MAY
 BE ADDED BY HAND.
  
 8) FL BLD CODE 1609.1.4 : COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS, ANCHOR TIES
 B) ROOFING ASSEMBLIES
  
 9) W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 10) SHEET S-1 INDICATES THE USE OF AN
 EXISTING ROOF DRAIN, IT APPEARS TO
 PENETRATE THE EXTERIOR WALL AND DRAIN
 INTO AN SCUPPER AND DOWN SPOUT SYSTEM.
 NO MENTION OF AN EMERGENCY OVERFLOW?
 1503.4.3
 WHEN OTHER MEANS OF DRAINAGE OF OVERFLOW
 WATER IS NOT PROVIDED, OVERFLOW SCUPPERS
 SHALL BE PLACED IN WALLS OR PARAPETS NOT
 LESS THAN 2 INCHES (51 MM) NOR MORE THAN
 4 INCHES (102 MM) ABOVE THE FINISHED
 ROOF COVERING AND SHALL BE LOCATED AS
 CLOSE AS PRACTICAL TO REQUIRED VERTICAL
 LEADERS OR DOWNSPOUTS OR WALL AND
 PARAPET SCUPPERS. AN OVERFLOW SCUPPER
 SHALL BE SIZED IN ACCORDANCE WITH THE
 FLORIDA BUILDING CODE, PLUMBING.
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026