Date Text
2006-09-09 00:00:00 
  
 DENIED
  
 1) PLEASE SHOW THE PYLON STRUCTURE ON
 THE DRAWINGS AND STATE IF 1 OR 2 SIDES
 WILL BE REPLACED
  
 2) THE CLAIMED VALUATION ON THE PERMIT
 APPLICATION IS LOW. FOR PERMITTING
 PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT
 COST EXCLUDING LAND VALUE. OUR VALUATION
 REFERENCE IS ICC (BVD), MARSHALL-SWIFT
 AND MEANS COST ANALYSIS SERVICES PER
 108.3 FBC*
  
 3) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MAY BE REQUIRED IF
 VALUATION IS DEEMED LOW, PRIOR TO A
 PERMIT BEING ISSUED
  