Plan Review Notes
Plan Review Notes For Permit 06082023
Permit Number 06082023
Review Stop E
Sequence Number 3
Notes
Date Text
2007-01-19 20:23:102007-01-19 20:23:10
  
 ** UNSAT 3RD REVIEW**
  
 ** THIS IS THE FIRST REVIEW UNDER PERMIT APPLICATION.
 THE TWO PREVIOUS REVIEWS WERE SUBMITTED UNDER *PLAN
 REVIEW*ONLY.
  
  
 1) NOTE: PLEASE SEE THE TWO PREVIOUS REVIEWS REQUESTED
 THE ENERGY CALCULATIONS MEET THE 2004 FBC 13-415.2 AND
 13-415.1.AB.1.1 AND TO CORRELATE WITH THE SUBMITTED
 ELECTRICAL PLANS.
 PLEASE KNOW THAT A MEETING WAS HELD ON JANUARY 10TH,
 2007 WHICH THE ENERGY CALCULATIONS WERE GONE OVER ALONG
 WITH THE PLANS. THESE WERE TO BE SUBMITTED FOR PERMIT
 APPLICATION THE SAME DAY. UPON REVIEW OF CALCULATIONS,
 THIS REVIEWER COMMENTED ON THE FACT THAT THE ENERGY
 CALCULATIONS IN THE INPUT DATA SECTION WAS STILL
 INDICATING *MANUAL ON/OFF* AND NEEDED TO CORRELATE WITH
 PLANS FOR *AUTOMATED* CONTROLS.
 PLEASE SEE THIS WAS NOT DONE.
 THERE WERE ALSO COMMENTS ON THE MISSING OVER RIDE TIMES
 ON THE T-OVER-RIDE DEVICES AND MOTION/OCCUPANCY SENSORS
 WHICH DID NOT INDICATE THE MAXIMUM TIMES AS REQUIRED
 AND PERMITTED BY THE CODE WHICH WAS IN THE TWO PREVIOUS
 REVIEW COMMENTS.
 IT WAS THE SUGGESTION OF THIS REVIEWER THAT THESE ITEMS
 MAY BE CORRECTED AND NEW SHEETS AND CALCULATIONS MAY BE
 SUBMITTED PRIOR TO THE ELECTRICAL REVIEW COMMENCING AS
 A BENEFIT AND TO ALLEVIATE ANY FURTHER DENIALS AND
 DELAYS IN THE PERMITTING.PLEASE KNOW THAT NEW
 ELECTRICAL SHEETS, A NEW STRUCTURAL SHEET AND ENERGY
 CALCULATIONS WERE BROUGHT INTO OUR OFFICE BY THE PERMIT
 EXPEDITOR AND WERE ALLOWED TO BE INSERTED INTO THE
 SETS.THIS REVIEWER HAD NOTICED THE ENERGY
 CALCULATIONS WERE SIGNED, AND CONTAINED A *RUBBER
 STAMP* FOR SEAL; HOWEVER THE REQUIRED RAISED EMBOSSED
 TYPE SEAL AS REQUIRED UNDER THE FLORIDA ADMINISTRATIVE
 CODE 61G15-23.001 WAS NOT VISIBLE WITH ANY INFORMATION
 ON SAID SEAL. IT WAS NOTED AND SUGGESED BY THIS
 REVIEWER ONCE AGAIN IN THE INTEREST OF NOT DELAYING THE
 PROJECT TO HAVE NEW SIGNED, DATED AND SEALED ENERGY
 CALCULATIONS BE SENT OVER NIGHT MAIL AND BROUGHT IN
 BEFORE REVIEW COMMENCED. THE NEW CALCULATIONS WERE
 SUBMITTED AND PLACED WITH PACKAGE FOR REVIEW. PLEASE
 SEE UPON REVIEW OF THE ENERGY CALCULATIONS, THE INPUT
 DATA STILL INDICATES * MANUAL ON/OFF* WHEN IN FACT
 THESE ARE OF AN *AUTOMATED* CONTROL. PLEASE SEE THAT
 THE FLA-COM DOES HAVE THE OPTION TO INSERT THE CORRECT
 INFORMATION FOR THIS AREA.
  
 ** PLEASE ALSO KNOW THAT UPON REVIEW OF SAID ENERGY
 CALCULATIONS, THESE ARE DATED NOVEMBER 27, 2006. IT IS
 UNCLEAR HOW THIS IS POSSIBLE WHEN THE MEETING TO GO
 OVER THESE CALCULATIONS AND PLANS DID NOT TAKE PLACE
 UNTIL JAN OF 07?
 A TECHNICAL REVIEW OF DOCUMENTS WAS NOT PERFORMED WHEN
 THESE TWO SUBMITTALS WERE BROUGHT IN BEFORE THIS
 REVIEW.
  
 2) NOTE: PLEASE SEE THE REVISED ELECTRICAL SHEETS WHICH
 WERE INSERTED INTO THE SETS. PLEASE SEE THE REQUIRED
 RAISED, EMBOSSED SEAL IS ILLEGIBLE AND NO INFORMATION
 ON SAID SEAL CAN BE MADE OUT EVEN BY USING A
 SHADOWING/DUSTING METHOD. THE RUBBER STAMPED SEAL IS
 NOT ACCEPTED IN THE STATE OF FLORIDA. FAC
 61G15-23.001.
  
 ** PLEASE ALSO SEE THESE SHEETS ARE ALSO DATED NOVEMBER
 27TH, 2006 WHICH IS NOT POSSIBLE ONCE AGAIN. PLEASE SEE
 THE REVISION DATES IN THE TITLE BLOCKS ALSO INDICATE
 11/27/06 WHICH IS NOT POSSIBLE WHEN THESE ARE RESPONSE
 TO COMMENTS FROM MEETING DATED 1/10/07 PLEASE SEE A
 RESPONSE LETTER FROM THE DESIGNER'S OFFICE DATED
 JANUARY 15TH, 2007 MENTIONS SOME RESPONSE(S) WHICH WERE
 NOT PART OF MY COMMENTS IN THE MEETING DATED JANUARY
 10TH, 2007. ( RESPONSE #4)
 PLEASE BE SURE ALL SHEETS ARE SIGNED, DATED AND SEALED
 CORRECTLY AND THE TITLE BLOCKS REFLECT THE CORRECT
 DATES WHEN PLANS WERE REVISED.
 FAC 61G15-23.002, FS 471.025
 FBC ADMIN SECTION 106.1
  
 3) NOTE: PLEASE ALSO SEE THAT AS OF THE MEETING DATED
 JANUARY 10TH, 2007 THE PREVIOUSLY REQUESTED DETAIL FOR
 TRANSFORMER MOUNTING WAS ALSO NOT SUBMITTED. IT WAS
 ONCE AGAIN STATED THAT THIS INFORMATION MAY BE BROUGHT
 IN WHEN INSERTING THE NEW REVISED ELECTRICAL SHEETS
 BEFORE THE ELECTRICAL REVIEW WAS TO COMMENCE. PLEASE
 SEE THE STRUCTURAL 8 1/2 X 11'S AND THE NEW *S* SHEETS
 IN SETS ARE MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER FOR THE ENGINEERING FIRM ON THE
 TITLE BLOCKS. PLEASE SEE FAC 61G15-23.002 AND FS
 471.023.
 THIS IS REQUIRED WHETHER OR NOT SHEETS WERE STAMPED FOR
 REVIEW OF CODE COMPLIANCE BY ANY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE SEE UPON REVIEW OF THE NEW FP SHEETS IN
 THE MEETING DATED JANUARY 10TH, 2007 IT WAS NOTED BY
 THIS REVIEWER THAT THE STROBE/HORN LEVELS DID NOT
 INDICATE THE REQUIRED MINIMUM LEVELS AS REQUIRED BY THE
 FBC 11-4.28.1,.2, .3(4). THIS WAS NEVER A COMMENT BY
 THIS REVIEWER AS THE RESPONSIBILITY OF THIS REVIEW WAS
 ONLY RECENTLY BEING HANDLED BY THE ELECTRICAL REVIEW.
 THE COMMENT WAS MADE IN THE MEETING THAT THE LEVELS
 WOULD BE REDLINED; HOWEVER AS THE PLANS ARE BEING
 DENIED AND GOING OUT FOR CORRECTIONS, PLEASE CORRECT
 AND REVISE THESE SHEETS AT THIS TIME WITH THE CORRECT
 MINIMUM LEVELS.
 FBC 106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE KNOW AS THIS PROJECT DID NOT APPLY FOR
 PERMIT UNTIL AFTER DECEMBER 7TH, 2006,ON DECEMBER
 8TH, 2006 THE STATE OF FLORIDA ADOPTED THE 2005
 NFPA-70. PLEASE ADJUST PLANS. THIS WAS GOING TO BE
 REDLINED AS STATED IN THE MEETING ON JAN 10TH, HOWEVER
 SINCE PLANS ARE COMING BACK PLEASE REVISE AT THIS TIME.
 THIS INCLUDES THE SHEET AT.1 WHICH CAN BE REDLINED.
 PLEASE ALSO SEE THAT THE 2006 REVISIONS TO THE 2004 FBC
 ALSO WENT INTO EFFECT ON THE SAME DATE. PLEASE CONFIRM
 CODE COMPLIANCE WITH CHAPTER 13, AS THERE WERE CHANGES,
 AND VERIFY ANY CHANGES WITH THE BUILDING CODE AND OTHER
 TRADES FOR POSSIBLE CHANGES.
 THIS IS REQUIRED WHETHER OR NOT COMMENTS ARE MADE BY
 OTHER TRADES.
 IF NO TECHNICAL CHANGES TO PLANS ARE REQUIRED, THEN THE
 CODE FOR THE 2006 REVISIONS TO THE 2004 FBC CAN ALSO BE
 HAND REDLINED ON AT.1
  
 6) NOTE: PLEASE SEE THAT THE SUBMITTED PLANS FOR THE
 FIRE SPRINKLER PLANS SHALL CONTAIN THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN AND
 WORK FOR THIS SCOPE.
 FBC 106.1.2, 106.3.5.1.2, 106.1.1.1
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT WAS MADE BY
 THE FIRE MARSHAL'S OFFICE.
  
 7) NOTE: PLEASE SEE THE ARCHITECTURAL SHEETS SHALL
 CONTAIN THE PRINTED NAME OF THE ARCHITECT. THIS CAN BE
 HAND PRINTED ON THE TITLE BLOCKS. THIS IS REQUIRED PER
 FAC 61G1-16.004.
 THIS IS REQUIRED EVEN IF ARCHITECTURAL PLANS HAVE BEEN
 STAMPED AS CODE COMPLIANT.
 THIS WAS IN THE ELECTRICAL REVIEW COMMENTS ON PREVIOUS
 REVIEWS. THIS IS REQUIRED.
  
 8) NOTE: ** PLEASE KNOW AS THE PLANS WERE SUBMITTED FOR
 * PLAN REVIEW* AND NOT FOR PERMIT THE 4X TIMES THE FEE
 FOR THE PLAN REVIEW PORTION OF THE BASE PERMIT FEE
 REPEAT CODE COMPLIANT COMMENTS HAS NOT BEEN ASSESSED AS
 REQUIRED PER FLORIDA STATUTES 553.80(2)(B). THIS IS
 ASSESSED WHEN PLANS HAVE BEEN SUBMITTED LEGALLY FOR
 PERMITTING.
 PLEASE KNOW HOWEVER THAT ONE SET OF EACH SET OF
 ELECTRICAL PLANS AND ENERGY CALCULATIONS ARE BEING
 RETAINED BY THIS OFFICE.
  
  
 **** PLEASE KNOW AS THIS REVIEWER WILL BE THE LICENSED
 REVIEWER TO ISSUE SAID PROJECT, IT IS THE
 RESPONSIBILITY OF THIS REVIEWER THAT COMPLIANCE FOR
 ISSUANCE OF PERMIT IS MET FOR ALL ASPECTS OF THE
 FLORIDA ADMINISTRATIVE CODE, FLORIDA STATUTES AND OTHER
 PERTINENT LAWS AND ORDINANCES.
 PLEASE ADDRESS THE ABOVE COMMENTS.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-01-19 17:58:042007-01-19 17:58:04
 NEW SHEETS AND ENERGY CALCULATIONS SUBMITTED 1/16. ALSO
 NEW ENERGY CALCULATIONS SUBMITTED AS A SUBMITTAL ON
 1/19.
 REVIEW IN PROGRESS.
2007-01-14 16:16:102007-01019 16:16:10
 ELECTRICAL REVIEW ON HOLD, WAITING FOR NEW SHEETS ALONG
 WITH NEW ENERGY CALCULATIONS BEFORE REVIEW STARTS. THIS
 IS AT THE REQUEST OF THE OWNER'S AND ARCHITECT. OTHER
 TRADES MAY REVIEW WHEN AVAILABLE.
 TO BE SUBMITTED ON 1/16