Date |
Text |
2006-10-30 18:26:06 | *** UNSAT 2ND REVIEW *** |
| |
| ** PLEASE KNOW, PLANS HAVE ONLY BEEN |
| SUBMITED FOR "PLAN REVIEW" AND HAVE NOT |
| BEEN SUBMITTED FOR PERMIT. |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| STILL IN NEED OF ADDRESSING. |
| PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| REVIEW. |
| |
| |
| |
| 1) NOTE: OK. |
| |
| 2) NOTE: OK. |
| |
| 3) NOTE: NO, PLEASE SEE THE FIRM NAME HAS BEEN |
| CORRECTED ON ALL SHEETS HOWEVER THE FIRM LICENSE NUMBER |
| AS REQUIRED ON PREVIOUS NOTES IS STILL NOT ON TITLE |
| BLOCKS AS REQUIRED. |
| |
| |
| ** PREVIOUS REVIEWNOTE ** |
| PLEASE CLARIFY TITLE BLOCKS FOR |
| THE ARHCITECTURAL FIRM. PLEASE SEE COVER |
| SHEET SHOWS "MBH " ARCHITECTS AND "A" |
| SHEETS INDICATE "DH" ARCHITECTS?? |
| PLEASE SEE MEP SHEETS DO INDICATE |
| "MDH"??? |
| PLEASE KNOW IN EITHER CASE, PLEASE SEE |
| MISSING REQUIRED LICENSE NUMBERS FOR |
| FIRM(S). PLEASE SEE FLORIDA |
| ADMINISTRATIVE CODE 61G1-16.004ANF |
| FLORIDA STATUS 481.219 FOR ARCHITECTURAL |
| FIRMS REQUIRING A CERTIFICATE OF |
| AUTHORIZATION NUMBER. |
| PLEASE ALSO SEE THE TITLE BLOCKS MISSING |
| THE REQUIRED PRINTED NAME AND LICENSE |
| NUMBER FOR THE ARCHITECT OF RECORD. |
| ** THIS IS REQUIRED ON ALL SHEETS AND |
| FOR ALL TRADES WHETHER OR NOT COMMENT IS |
| MADE BY OTHER REVIEWER(S). |
| |
| 4) NOTE:NO, PLEASE SEE NUMEROUS SHEETS WHICH WERE NOT |
| DATED BY THE ARCHITECT. |
| PLEASE KNOW THIS IS REQUIRED WHICH LENDS TO THE |
| AUTHENTICITY OF THE PLANS WHICH ARE BEING SIGNED AND |
| SEALED. |
| PLEASE ALSO BE SURE ALL SEALS ARE "RAISED" SO THAT ALL |
| INFORMATION ON SAID SEAL IS CLEAR AND VISABLE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE FS 481.221 WHICH |
| REQUIRES THE ARCHITECT TO DATE SAID |
| PLANS WHEN SIGNING AND SEALING |
| DOCUMENTS. |
| |
| 5) NOTE: OK. |
| |
| 6) NOTE:NO, PLEASE SEE SEPERATE SPACES. |
| PLEASE SEE LIGHTING ALLOWED AND DEISGNED, SHOWN, |
| HOWEVER WHERE ARE THESE FIGURES FROM AND WHAT ARE THEY? |
| " X" PER SQ FT, PER RETAIL , STOCK AREA ETC. |
| PLEASE SEE MISSING CONTROLS AT LOCATION OF INGRESS INTO |
| SPACE. |
| |
| ** PREVIUOUS REVIEW NOTE ** |
| PLEASE SEE LIGHTING CONTROL |
| CONTACTORS ARE BEING SHOWN , HOWEVER |
| COULD NOT LOCATE THE AUTOMATIC SHUT OFF |
| FOR LIGHTING CONTROLS AS REQUIRED UNDER |
| FBC 2004 CHAPTER 13. |
| PLEASE SEE MISSING THE SCHEDULING, |
| OVER-RIDE DEVICES. |
| PLEASE SEE SEPARATE SPACES WITH FLR TO |
| CEILING HEIGHT PARTITIONS WHICH REQUIRE |
| OVER RIDES OF THE NORMAL LC SYSTEM. |
| PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 |
| AND .1.3. |
| PLEASE SUPPLY THE LIGHTING POWER DENSITY CALCULATIONS |
| AS SETFORTH IN |
| 13-415.2.ABC.1 AND TABLE 415.2.B.1, |
| 415.2.C.1 |
| ** PLEASE KNOW OVER-RIDES SHALL BE |
| LOCATED SO THE OCCUPANT CAN SEE LIGTHING |
| BEING CONTROLLED FOR MAIN SYSTEM. |
| PLEASE SPECIFY THE OVER-RIDE DEVICES, IF |
| TIMER TYPE (4HRS MAX) , IF OCCUPANT |
| SENSOR TYPE (30MINS MAX). |
| ** PLEASE KNOW, ANY LIGHTING BEING LEFT |
| IN THE "ON" POSITION INTENDED AS NIGHT |
| LTS SHOULD BE KEPT TO A MINIMUM. PLEASE |
| SEE THE STORE FRONT WOULD BE ACCEPTABLE |
| , HOWEVER ALL OTHER TRACK LIGHTING |
| SHOULD BE SHUT OFF WITH THE AUTOMATED |
| LIGHTING |
| CONTROLS. PLEASE SEE THAT THIS NUMBER OF |
| FIXTURES CAN BE GONE OVER. THE AMOUNT OF |
| FIXTURES SHOWN EXCEEDS THAT REQUIRED BY |
| THE FEC FOR THIS AHJ'S INTERPRETATION. |
| |
| 7) NOTE: NO? , SAME NOTE AS ONLY MENTIONED BY THE |
| ELECTRICLA REVIEWER. |
| IF THIS IS A CODE VIOLATION, PLANS WILL BE REQUIRED TO |
| BE MODIFIED. |
| |
| ** PREVIOUS REVIEW NOTE** PLEASE SEE POSSIBLE NOTES |
| FROM BUILDING/PLUMBING REVIEW AS THE ACCESS |
| TO THE HC BATHS SEEMS TO BE LOCATED |
| THROUGH THE "STOCKROOM". THIS IS NOT AN |
| ELECTRICAL REVIEW NOTE, HOWEVER A CLEAR |
| AND UNOBSTRUCTED PATH MAY NOT EXIST FOR |
| FIRE EGRESS ETC.?? |
| THIS IS ONLY NOTED. |
| |
| 8) NOTE: OK. |
| |
| 9) NOTE:OK/NO., PLEASE SEE UNIT IS NOW BEING SHOWN |
| BELOW CEILING, HOWEVER NO DETAIL FOR STRUCTURAL REVIEW |
| WAS SUBMITTED AND IS NOTED TO BE DONE AT A LATER DATE. |
| PLEASE KNOW THIS IS REQUIRED AT THIS TIME AS IF THE |
| LCOATION AS SHOWN IS NOT SUFFICIENT OR AFFECT THE |
| STRUCTURAL INTEGRITY OF THE EXISTIGN STRUCTURE, THE |
| LOCATION MAY NEED TO BE CHANGED THEREFORE, REVISON OF |
| ELECTRICLA AND POSSIBLE ITEMS PER |
| 450.9,450.13,110.26,240.21 MAY NEED TO BE REVIEWED. |
| ** PLEASE SUBMIT AT THSI TIME. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THE TRANSFORMER IS |
| BEING SHOWN ON THE RISER LOCATED ABOVE |
| THE CEILING WHICH IS NOT PERMITTED PER |
| 450.13B. |
| PLEASE PROVIDE AN ALTERNATE LOCATION. |
| PLEASE SEE 450.9, 450.21A |
| ** PLEASE ALSO SUBMIT A STRUCTURAL |
| ENGINEERING DETAIL FOR THE SUPPORT AND |
| MOUNTING OF UNIT. |
| FBC 106.1.2 |
| |
| 10) NOTE: OK. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |
| |
2006-10-30 09:58:23 | REMOVED FROM INCOMING, IN ELECTRICAL FOR REVIEW. |