Plan Review Notes
Plan Review Notes For Permit 06082023
Permit Number 06082023
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-30 18:26:06*** UNSAT 2ND REVIEW ***
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
 PLEASE SEE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW.
  
  
  
 1) NOTE: OK.
  
 2) NOTE: OK.
  
 3) NOTE: NO, PLEASE SEE THE FIRM NAME HAS BEEN
 CORRECTED ON ALL SHEETS HOWEVER THE FIRM LICENSE NUMBER
 AS REQUIRED ON PREVIOUS NOTES IS STILL NOT ON TITLE
 BLOCKS AS REQUIRED.
  
  
 ** PREVIOUS REVIEWNOTE **
 PLEASE CLARIFY TITLE BLOCKS FOR
 THE ARHCITECTURAL FIRM. PLEASE SEE COVER
 SHEET SHOWS "MBH " ARCHITECTS AND "A"
 SHEETS INDICATE "DH" ARCHITECTS??
 PLEASE SEE MEP SHEETS DO INDICATE
 "MDH"???
 PLEASE KNOW IN EITHER CASE, PLEASE SEE
 MISSING REQUIRED LICENSE NUMBERS FOR
 FIRM(S). PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004ANF
 FLORIDA STATUS 481.219 FOR ARCHITECTURAL
 FIRMS REQUIRING A CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE ALSO SEE THE TITLE BLOCKS MISSING
 THE REQUIRED PRINTED NAME AND LICENSE
 NUMBER FOR THE ARCHITECT OF RECORD.
 ** THIS IS REQUIRED ON ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4) NOTE:NO, PLEASE SEE NUMEROUS SHEETS WHICH WERE NOT
 DATED BY THE ARCHITECT.
 PLEASE KNOW THIS IS REQUIRED WHICH LENDS TO THE
 AUTHENTICITY OF THE PLANS WHICH ARE BEING SIGNED AND
 SEALED.
 PLEASE ALSO BE SURE ALL SEALS ARE "RAISED" SO THAT ALL
 INFORMATION ON SAID SEAL IS CLEAR AND VISABLE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FS 481.221 WHICH
 REQUIRES THE ARCHITECT TO DATE SAID
 PLANS WHEN SIGNING AND SEALING
 DOCUMENTS.
  
 5) NOTE: OK.
  
 6) NOTE:NO, PLEASE SEE SEPERATE SPACES.
 PLEASE SEE LIGHTING ALLOWED AND DEISGNED, SHOWN,
 HOWEVER WHERE ARE THESE FIGURES FROM AND WHAT ARE THEY?
 " X" PER SQ FT, PER RETAIL , STOCK AREA ETC.
 PLEASE SEE MISSING CONTROLS AT LOCATION OF INGRESS INTO
 SPACE.
  
 ** PREVIUOUS REVIEW NOTE **
 PLEASE SEE LIGHTING CONTROL
 CONTACTORS ARE BEING SHOWN , HOWEVER
 COULD NOT LOCATE THE AUTOMATIC SHUT OFF
 FOR LIGHTING CONTROLS AS REQUIRED UNDER
 FBC 2004 CHAPTER 13.
 PLEASE SEE MISSING THE SCHEDULING,
 OVER-RIDE DEVICES.
 PLEASE SEE SEPARATE SPACES WITH FLR TO
 CEILING HEIGHT PARTITIONS WHICH REQUIRE
 OVER RIDES OF THE NORMAL LC SYSTEM.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2
 AND .1.3.
 PLEASE SUPPLY THE LIGHTING POWER DENSITY CALCULATIONS
 AS SETFORTH IN
 13-415.2.ABC.1 AND TABLE 415.2.B.1,
 415.2.C.1
 ** PLEASE KNOW OVER-RIDES SHALL BE
 LOCATED SO THE OCCUPANT CAN SEE LIGTHING
 BEING CONTROLLED FOR MAIN SYSTEM.
 PLEASE SPECIFY THE OVER-RIDE DEVICES, IF
 TIMER TYPE (4HRS MAX) , IF OCCUPANT
 SENSOR TYPE (30MINS MAX).
 ** PLEASE KNOW, ANY LIGHTING BEING LEFT
 IN THE "ON" POSITION INTENDED AS NIGHT
 LTS SHOULD BE KEPT TO A MINIMUM. PLEASE
 SEE THE STORE FRONT WOULD BE ACCEPTABLE
 , HOWEVER ALL OTHER TRACK LIGHTING
 SHOULD BE SHUT OFF WITH THE AUTOMATED
 LIGHTING
 CONTROLS. PLEASE SEE THAT THIS NUMBER OF
 FIXTURES CAN BE GONE OVER. THE AMOUNT OF
 FIXTURES SHOWN EXCEEDS THAT REQUIRED BY
 THE FEC FOR THIS AHJ'S INTERPRETATION.
  
 7) NOTE: NO? , SAME NOTE AS ONLY MENTIONED BY THE
 ELECTRICLA REVIEWER.
 IF THIS IS A CODE VIOLATION, PLANS WILL BE REQUIRED TO
 BE MODIFIED.
  
 ** PREVIOUS REVIEW NOTE** PLEASE SEE POSSIBLE NOTES
 FROM BUILDING/PLUMBING REVIEW AS THE ACCESS
 TO THE HC BATHS SEEMS TO BE LOCATED
 THROUGH THE "STOCKROOM". THIS IS NOT AN
 ELECTRICAL REVIEW NOTE, HOWEVER A CLEAR
 AND UNOBSTRUCTED PATH MAY NOT EXIST FOR
 FIRE EGRESS ETC.??
 THIS IS ONLY NOTED.
  
 8) NOTE: OK.
  
 9) NOTE:OK/NO., PLEASE SEE UNIT IS NOW BEING SHOWN
 BELOW CEILING, HOWEVER NO DETAIL FOR STRUCTURAL REVIEW
 WAS SUBMITTED AND IS NOTED TO BE DONE AT A LATER DATE.
 PLEASE KNOW THIS IS REQUIRED AT THIS TIME AS IF THE
 LCOATION AS SHOWN IS NOT SUFFICIENT OR AFFECT THE
 STRUCTURAL INTEGRITY OF THE EXISTIGN STRUCTURE, THE
 LOCATION MAY NEED TO BE CHANGED THEREFORE, REVISON OF
 ELECTRICLA AND POSSIBLE ITEMS PER
 450.9,450.13,110.26,240.21 MAY NEED TO BE REVIEWED.
 ** PLEASE SUBMIT AT THSI TIME.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE TRANSFORMER IS
 BEING SHOWN ON THE RISER LOCATED ABOVE
 THE CEILING WHICH IS NOT PERMITTED PER
 450.13B.
 PLEASE PROVIDE AN ALTERNATE LOCATION.
 PLEASE SEE 450.9, 450.21A
 ** PLEASE ALSO SUBMIT A STRUCTURAL
 ENGINEERING DETAIL FOR THE SUPPORT AND
 MOUNTING OF UNIT.
 FBC 106.1.2
  
 10) NOTE: OK.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
2006-10-30 09:58:23REMOVED FROM INCOMING, IN ELECTRICAL FOR REVIEW.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved