Plan Review Notes
Plan Review Notes For Permit 06082023
Permit Number 06082023
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-10 00:00:00*** UNSAT ***
  
 ** PLEASE KNOW, PLANS HAVE ONLY BEEN
 SUBMITED FOR "PLAN REVIEW" AND HAVE NOT
 BEEN SUBMITTED FOR PERMIT.
  
 ** PLEASE CORRECT ADDRESS AND SUITE/UNIT
 NUMBER ON ALL SHEETS IN CADD/PROGRAM.
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES
 ARE REQUIRED AT A MINIMUM.
 2002 NFPA-70 (NEC), 2002 NFPA-72, 2003
 NFPA-101.
 THESE SHOULDS ALSO BE LOCATED IN NOTE ON ELECTRICAL
 PLANS 16A.
  
 2) NOTE: PLEASE BE SURE WHEN SUBMITTING
 PLANS TO ATTACH ALL SHEETS TOGETHER INTO
 TWO COMPLETE SETS. PLEASE SEE THAT PLANS
 WERE SUBMITTED AS LOOSE SHEETS AND WERE
 ATTACHED INTO SETS BY THIS OFFICE THIS
 TIME AS A COURTESY.
 FBC 106.1 ADMIN SECT.
  
 3) NOTE: PLEASE CLARIFY TITLE BLOCKS FOR
 THE ARHCITECTURAL FIRM. PLEASE SEE COVER
 SHEET SHOWS "MBH " ARCHITECTS AND "A"
 SHEETS INDICATE "DH" ARCHITECTS??
 PLEASE SEE MEP SHEETS DO INDICATE
 "MDH"???
 PLEASE KNOW IN EITHER CASE, PLEASE SEE
 MISSING REQUIRED LICENSE NUMBERS FOR
 FIRM(S). PLEASE SEE FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004ANF
 FLORIDA STATUS 481.219 FOR ARCHITECTURAL
 FIRMS REQUIRING A CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE ALSO SEE THE TITLE BLOCKS MISSING
 THE REQUIRED PRINTED NAME AND LICENSE
 NUMBER FOR THE ARCHITECT OF RECORD.
 ** THIS IS REQUIRED ON ALL SHEETS AND
 FOR ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 4) NOTE: PLEASE SEE FS 481.221 WHICH
 REQUIRES THE ARCHITECT TO DATE SAID
 PLANS WHEN SIGNING AND SEALING
 DOCUMENTS.
  
 5) NOTE: PLEASE CLARIFY ENGINEERING
 TITLE BLOCKS AND RESPONSIBLE PARTIES.
 PLEASE SEE COVERSHEET LIST "HBK
 ENGINEERING", YET MEP'S DO NOT CONTAIN
 THE SAME TITLE BLOCK??
 PLEASE ALSO SEE MISSING CERTIFICATE OF AUTHORIZATION
 NUMBER FOR SAID
 ENGINEERING FIRM.
 FAC 61G15-23.002, FS 471.023
  
 6) NOTE: PLEASE SEE LIGHTING CONTROL
 CONTACTORS ARE BEING SHOWN , HOWEVER
 COULD NOT LOCATE THE AUTOMATIC SHUT OFF
 FOR LIGHTING CONTROLS AS REQUIRED UNDER
 FBC 2004 CHAPTER 13.
 PLEASE SEE MISSING THE SCHEDULING,
 OVER-RIDE DEVICES.
 PLEASE SEE SEPARATE SPACES WITH FLR TO
 CEILING HEIGHT PARTITIONS WHICH REQUIRE
 OVER RIDES OF THE NORMAL LC SYSTEM.
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2
 AND .1.3.
 PLEASE SUPPLY THE LIGHTING POWER DENSITY CALCULATIONS
 AS SETFORTH IN
 13-415.2.ABC.1 AND TABLE 415.2.B.1,
 415.2.C.1
 ** PLEASE KNOW OVER-RIDES SHALL BE
 LOCATED SO THE OCCUPANT CAN SEE LIGTHING
 BEING CONTROLLED FOR MAIN SYSTEM.
 PLEASE SPECIFY THE OVER-RIDE DEVICES, IF
 TIMER TYPE (4HRS MAX) , IF OCCUPANT
 SENSOR TYPE (30MINS MAX).
 ** PLEASE KNOW, ANY LIGHTING BEING LEFT
 IN THE "ON" POSITION INTENDED AS NIGHT
 LTS SHOULD BE KEPT TO A MINIMUM. PLEASE
 SEE THE STORE FRONT WOULD BE ACCEPTABLE
 , HOWEVER ALL OTHER TRACK LIGHTING
 SHOULD BE SHUT OFF WITH THE AUTOMATED
 LIGHTING
 CONTROLS. PLEASE SEE THAT THIS NUMBER OF
 FIXTURES CAN BE GONE OVER. THE AMOUNT OF
 FIXTURES SHOWN EXCEEDS THAT REQUIRED BY
 THE FEC FOR THIS AHJ'S INTERPRETATION.
  
 7) NOTE: PLEASE SEE POSSIBLE NOTES FROM
 BUILDING/PLUMBING REVIEW AS THE ACCESS
 TO THE HC BATHS SEEMS TO BE LOCATED
 THROUGH THE "STOCKROOM". THIS IS NOT AN
 ELECTRICAL REVIEW NOTE, HOWEVER A CLEAR
 AND UNOBSTRUCTED PATH MAY NOT EXIST FOR
 FIRE EGRESS ETC.??
 THIS IS ONLY NOTED.
  
 8) NOTE: PLEASE SEE A SYMBOL IS BEING
 SHOWN ON THE LIGHTING PLAN E2.00,
 HOWEVER THIS SYMBOL COULD NOT BE LOCATED
 ON THE PLANS/SCHEDULE/SYMBOL LIST.
 THIS HAS BEEN REDLINED ON PLANS ON ONE
 SET TO CLARIFY??
 106.1.2 FBC ADMIN SECT.
  
 9) NOTE: PLEASE SEE THE TRANSFORMER IS
 BEING SHOWN ON THE RISER LOCATED ABOVE
 THE CEILING WHICH IS NOT PERMITTED PER
 450.13B.
 PLEASE PROVIDE AN ALTERNATE LOCATION.
 PLEASE SEE 450.9, 450.21A
 ** PLEASE ALSO SUBMIT A STRUCTURAL
 ENGINEERING DETAIL FOR THE SUPPORT AND
 MOUNTING OF UNIT.
 FBC 106.1.2
  
 10) NOTE: PLEASE KNOW, ANY LOCK-OFF
 DEVICE BEING PROPOSED FOR CIRCUITS,
 SHALL BE AN INTEGRAL PART OF THE BREAKER
 WHERE REQUIRED BY CODE. PLEASE KNOW THE
 DEVICE TYPE CAN NOT JUST SIMPLY FALL OFF
 UPON THE REMOVAL OF THE PANEL COVERS, OR
 SNAP ON TO THE BRKR.
 ** WHERE REQUIRED BY CODE FOR CIRCUITS,
 OPTIONAL CIRCUITS DO NOT APPLY.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  