Plan Review Notes For Permit 06082019 |
Permit Number |
06082019 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-09-27 00:00:00 | *** DENIED *** | | 1) ENERGY CALCULATIONS ARE CALLING FOR | | TWO 12 SEER A/C SYSTEMS, AND THE MECH. | | PLANS ARE CALLING FOR TWO 12 SEER A/C | | SYSTEMS, THE TWO MUST COINCIDE, PLEASE | | CORRECT. | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED | | BY OWNER/AGENT ALSO, PER 2004 FBC | | 13-600.3.ABC.2 . | | | | 3) PLEASE NOTE ON MECHANICAL PLANS, | | CLOTHES DRYER VENT TERMINATION MUST BE A | | MIN. OF 4 FT. FROM A/C CONDENSER UNIT, | | PER 2004 FBC/M 501.2 . | | | | 4) PLEASE REMOVE NOTE ON MECH. PLANS | | UNDER EQUIPMENT LISTING REGARDING 1 CFM | | PER SQ. FT.. | | | | 5) PLEASE SHOW THE SIZE OF THE RETURN | | AIR GRILL FOR AHU #1 ON MECH. PLANS. | | | | 6) PLEASE LABEL AHU #1 LOCATION ON MECH. | | PLANS. | | | | 7) SEE HIGH LIGHTS ON MECH. PLANS, | | PLEASE CORRECT. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|