2006-09-09 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- PROVIDE KEY PLAN AND WINDOWS AND |
| DOORS SIZES. TO VERIFY EGRESS |
| COMPLIANCE. SEC. 106.1.2 CITY AMENDMENTS |
| TO FBC 2004. |
| |
| 2- PROVIDE OPENING PROTECTION (SHUTTERS |
| OR ANY OTHER MEANS OF GLAZING |
| PROTECTION) AS REQUIRED BY SECTION 507.3 |
| FBC 2004, EXISTING BUILDING. |
| PROVIDE PRODUCT APPROVAL, KEY PLAN AND A |
| COMPLETE INSTALLATION SCHEDULE. SEE |
| ATTACHED SAMPLE OF INSTALLATION SCHEDULE |
| FROM THE CITY IMPLEMENTATION STANDARD |
| FOR WIND-BORNE DEBRIS IMPACT PROTECTION. |
| |
| 3- ACCORDING TO INSPECTOR'S |
| PRE-INSPECTION AND PICTURES BUILDING HAS |
| ROTTEN AREAS AT OPENINGS FRAMING. NEED |
| TO REPLACE FRAMING AS REQUIRED. PROVIDE |
| COMPLETE STRUCTURAL FRAMING DETAILS FOR |
| DOORS AND WINDOWS INSTALLATION. SEC. |
| 106.1.2 OF CITY AMENDMENTS TO FBC 2004. |
| |
| 4- THIS PERMIT APPLICATION IS FOR DOORS |
| AND WINDOWS REPLACEMENT ONLY. ACCORDING |
| TO THE INSPECTOR'S PICTURES THERE IS |
| CONSIDERABLE STRUCTURAL DAMAGE TO THE |
| HOUSE. PROVIDE COMPLETE ENGINEERING AND |
| STRUCTURAL PLANS TO PERFORM ALL |
| STRUCTURAL REPAIRS. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004. |
| |
| 5- THERE ARE 2 DIFFERENT PRODUCT |
| APPROVALS FOR DOORS SUBMITTED. SUBMIT |
| ONLY THE ONE FOR THE SPECIFIC DOOR TO BE |
| INSTALLED. |
| |