2007-11-02 16:25:14DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 A SEPARATE GAS PERMIT IS REQUIRED
  
 FROM THE PREVIOUS REVIEWS:
 ****FROM PREVIOUS REVIEWS:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS PERMIT:
  
 1. OK
 2. OK
  
 3. TYPE OF GAS (NATURAL SHOWN ON
 GENERATOR SPECIFICATION SHEETS. INDICATE
 ON ISOMETRIC).
 ****RESPONSE NOTED, BUT THERE IS A CONFLICT OF
 INFORMATION SUBMITTED, APPLICATION AND PLANS INDICATE
 AND LP SYSTEM WITH AN UNDERGROUND 1000 GAL LP TANK. THE
 INFORMATION SUBMITTED UNDER THE RISER DIAGRAM STATES
 NATURAL GAS. PLEASE CLARIFY.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 ****RESPONSE NOTED, BUT THE BTU'S INDICATED ON THE
 INFORMATION UNDER THE RISER DIAGRAM STATES 273,120
 BTU"S/PER HR, BUT THE MANUF. SPECIFICATIONS SHEETS
 INDICATE 1,100 CUBIC FT/HR. . MANUF SPECIFICATION
 SHEETS ALSO INDICATE NATURAL GAS. NO LP GAS IS
 INDICATED. PLEASE CLARIFY.
  
 5. OK
 6.OK
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 INSTALLATION REQUIREMENTS SHALL BE
 SUBMITTED TO VERIFY CLEARANCES FROM
 ADJACENT STRUCTURES.
 ****INSTALLATION INSTRUCTIONS HAVE NOT BEEN SUBMITTED
 WITH THE MANUF. SPECIFICATION SHEETS.
 ******INSTALLATION INSTRUCTIONS WITH REQUIRED
 CLEARANCES HAV NOT BEEN SUBMITTED.
  