Date |
Text |
2007-11-02 16:25:14 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| A SEPARATE GAS PERMIT IS REQUIRED |
| |
| FROM THE PREVIOUS REVIEWS: |
| ****FROM PREVIOUS REVIEWS: |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR THE GAS PERMIT: |
| |
| 1. OK |
| 2. OK |
| |
| 3. TYPE OF GAS (NATURAL SHOWN ON |
| GENERATOR SPECIFICATION SHEETS. INDICATE |
| ON ISOMETRIC). |
| ****RESPONSE NOTED, BUT THERE IS A CONFLICT OF |
| INFORMATION SUBMITTED, APPLICATION AND PLANS INDICATE |
| AND LP SYSTEM WITH AN UNDERGROUND 1000 GAL LP TANK. THE |
| INFORMATION SUBMITTED UNDER THE RISER DIAGRAM STATES |
| NATURAL GAS. PLEASE CLARIFY. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| ****RESPONSE NOTED, BUT THE BTU'S INDICATED ON THE |
| INFORMATION UNDER THE RISER DIAGRAM STATES 273,120 |
| BTU"S/PER HR, BUT THE MANUF. SPECIFICATIONS SHEETS |
| INDICATE 1,100 CUBIC FT/HR. . MANUF SPECIFICATION |
| SHEETS ALSO INDICATE NATURAL GAS. NO LP GAS IS |
| INDICATED. PLEASE CLARIFY. |
| |
| 5. OK |
| 6.OK |
| 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| INSTALLATION REQUIREMENTS SHALL BE |
| SUBMITTED TO VERIFY CLEARANCES FROM |
| ADJACENT STRUCTURES. |
| ****INSTALLATION INSTRUCTIONS HAVE NOT BEEN SUBMITTED |
| WITH THE MANUF. SPECIFICATION SHEETS. |
| ******INSTALLATION INSTRUCTIONS WITH REQUIRED |
| CLEARANCES HAV NOT BEEN SUBMITTED. |
| |
| ************NEW COMMENT************* |
| |
| 1B. OK |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |