2007-09-22 12:12:38 | |
| ** DENIED 4TH REVIEW** |
| |
| ** PLEASE SEE THERE ARE SOME ITEMS FROM PREVIOUS REVIEW |
| WHICH ARE STILL IN NEED OF ADDRESSING. |
| PLEASE KNOW THERE ARE SOME ITEMS WHICH COULD BE |
| REDLINED. |
| |
| 1) NOTE: PLEASE SEE CODE STATED IN THE 2005 WHEN |
| PROJECT IS UNDER 2002 NEC> ALSO STATES 220.83 WHICH IS |
| FOR RESIDENTIAL. |
| THESE COULD BE REDLINED HOWEVER COMMENTS ARE MADE AT |
| THIS TIME FOR OTHER ITEMS. |
| |
| 2) NOTE: PLEASE SEE THE LOAD BASED ON ONE YEAR IS |
| ACTUALLY HIGHER THAN THE RATING OF THE GENERATOR. |
| HOW WILL THIS BE ADDRESSED? WILL LOADS BE SHED? |
| 702.5, 220.87 |
| |
| 3) NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS REVIEW. |
| PLEASE PROVIDE DOCUMENTATION FOR THE NEW MTSAND |
| WHETHER OR NOT THIS IS SERVICE ENTRANCE RATED. BASED ON |
| THE MANUFACTURES SPECS/CUT SHEETS SUBMITTED THERE IS |
| NOT INFORMATION ON THIS. |
| 230, 110.3, 90.7, 230.76, 230.79 ETC, |
| |
| 4) NOTE: PLEASE SEE THE RISER INDICATES *EQUIPMENT |
| GROUNDING CONDUCTORS* FROM METER TO THE MTS. IF THE MTS |
| IS SERVICE ENTRANCE RATED AND IS THE FIRST MEANS OF |
| DISCONNECT, AN *EGC* IS NOT PERMITTED BEFORE THE FIRST |
| MEANS OF DISCONNECT. |
| THIS COULD BE REDLINED HOWEVER PLANS HAVE OTHER NOTES. |
| |
| 5) NOTE: PLEASE CLARIFY WHERE THE ELEVATION OF NEW SLAB |
| IS LOCATED ON PLANS? |
| PLEASE SEE BUILDING REVIEW COMMENTS ALSO, AS THIS IS |
| REQUIRED TO BE 6INCHES ABOVE ANY BASE FLOOD ELEVATION |
| IF THIS IS LOCATED IN A FLOOD ZONE A. |
| ** IT WAS NOTED THE RESPONSE MENTIONS AN ELEVATION |
| CERTIFICATE WILL BE SUBMITTED HOWEVER IT IS THE |
| UNDERSTANDING THE ELEVATION WILL BE NEEDED ON SHEETS. |
| ** SEE BUILDING REVIEW NOTES** |
| |
| 6) NOTE: PLEASE SEE NO VALUE FOR GAS SCOPE OF WORK |
| APPLICATION IS STATED. |
| PLEASE SEE THE VALUE FOR THE COMPLETE SCOPE OF WORK |
| MUST INCLUDE ALL LABOR AND MATERIALS, INCLUDING |
| EQUIPMENT ETC |
| FBC 108.3 |
| AS THE SCOPE OF WORK HAS INCREASED SINCE ORIGINAL |
| PERMIT APPLICATION, PLEASE ADJUST. |
| |
| 7) NOTE: THE NOTICE OF COMMENCEMENT WHICH WAS SUBMITTED |
| RECORDED ON 3/14/07 HAS BECOME VOID PER FS 713.13(2). |
| WHEN WORK HAS NOT COMMENCES WITHIN 90DAYS OF RECORDING |
| THE NOC, THE NOC BECOMES VOID. |
| **THIS WILL ONLY NEED TO BE RE-RECORDED AND SUBMITTED |
| PRIOR TO PICKING UP THE PERMIT ONCE ISSUED. |
| |
| 8) NOTE: PLANS NOW MENTIONS BUILDING OF NEW WALL, |
| HOWEVER NO PLANS FOR WALL ETC WAS SUBMITTED. PLEASE SEE |
| COMMENTS FROM OTHER TRADES AS THIS IS NOT AND |
| ELECTRICAL REVIEW ITEM. PLEASE ONLY KNOW THE |
| CONSTRUCTION OF WALL MAY NOT BE DONE UNDER THE |
| ELECTRICAL U LICENSE. |
| |
| ** PLEASE KNOW SOME OF THE ABOVE ITEMS COULD HAVE BEEN |
| REDLINED, HOWEVER PLANS NEEDED SOME OTHER ITEMS TO BE |
| ADDRESSED AT THIS TIME. |
| |
| ** PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES WHICH |
| MAY AFFECT ELECTRICAL PLANS OR DESIGN. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| |
| *** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS |
| OR COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. |
| IF THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY |
| WAY, NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, |
| PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE AND |
| THIS REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |