Date |
Text |
2007-03-25 09:15:02 | |
| |
| ****** UNSAT 3ND REVIEW****** |
| |
| ** PLEASE KNOW THAT ANY REFERENCE TO THE FBC CHAPTER 1 |
| IN THE PLAN REVIEW COMMENTS CAN BE FOUND IN THE |
| ADMINISTRATIVE SECTION OF THE 2004 FBC AS ADOPTED BY |
| THE CITY OF WEST PALM BEACH. |
| |
| ** PLEASE SEE THAT THERE COMMENTS MADE TO SHEETS OTHER |
| THAN ELECTRICAL BY THIS REVIEW. THESE COMMENTS ARE |
| REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY OTHER |
| TRADE. |
| |
| ** IMPORTANT** |
| DUE TO MANY OF THE COMMENTS BELOW ONE COMPLETE SET OF |
| EACH PLAN SUBMITTED ARE BEING RETAINED BY THIS OFFICE. |
| PLEASE ALSO SEE THAT COMMENTS FROM PREVIOUS REVIEW |
| STILL NEED TO BE ADDRESSED ALONG WITH NEW COMMENTS DUE |
| TO PLANS CHANGING. |
| |
| 1) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS WITH |
| ALL INFORMATION IN TWO NEAT AND ORDERLY SETS. PLEASE |
| SEE THE SHEETS SUBMITTED ARE IN COMPLETE DISARRAY WITH |
| MANY SHEETS LOOSE AND NOT IN ANY SETS OR BOUND |
| TOGETHER?? |
| ** PLEASE SEE THERE IS MULTIPLE ELECTRICAL RISERS YET |
| SOME CONTAIN THE SAME DATE OF THE PREVIOUS RISER |
| DIAGRAM SUBMITTED. PLEASE CORRELATE ALL PLANS, SHEETS, |
| DATE THE REVISED SHEETS. THE PLANS WHICH SEEMED TO BE |
| REVISED SHEETS CONTAIN A DATE OF JANUARY 10, 2007 |
| HOWEVER THAT DATESBEFORE THE LAST ELECTRICAL REVIEW |
| WHICH WAS DONE ON 2/2/07.THE PREVIOUS REVIEWED PLANS |
| ALSO CONTAINED A DATE OF 1/10/07??? |
| FBC 106.3 |
| |
| 2) NOTE: PLEASE SEE THE PLANS SUBMITTED STILL DO NOT |
| INDICATE THE CORRECT CODES RELEVANT TO THE PLANS AND |
| DESIGNS AT A MINIMUM AS REQUESTED ON THE TWO PREVIOUS |
| REVIEWS. PLEASE SEE THE CODES REQUESTED ARE FOR THIS |
| REVIEWER ONLY AND OTHER CODES FROM OTHER TRADES MAY BE |
| NEEDED. |
| |
| 3) NOTE: PLEASE SEE THE REQUIRED GAS RISER PLANS WERE |
| NOT SUBMITTED IN PACKAGE FOR PLUMBING REVIEW. SEE |
| PLUMBING REVIEW COMMENTS. |
| FBC 106.1.2 |
| |
| 4) NOTE: PLEASE SEE THE MODEL OF THE GENERATOR IS STILL |
| NOT INDICATED ON THE MANUFACTURES SPECS/CUT SHEETS |
| SUBMITTED AND NOW THE BREAKER ON THE RISER DIAGRAM ON |
| THE GENERATOR HAS NOW INCREASED WHICH NOW CORRELATES TO |
| THE SINGLE PHASE GENERATOR ON SPECS? |
| PLEASE SPECIFY WHICH UNIT IS BEING INSTALLED, PLEASE |
| HIGHLIGHT UNIT, PLEASE REVISE RISER IF INDEED THIS IS |
| NOW THE SINGLE PHASE UNIT AS IT SEEMS.PLEASE SEE THE |
| FOLLOWING COMMENT #5. |
| 110.3, 90.7 |
| FBC 106.3.5.1.2 |
| |
| 5) NOTE: PLEASE SEE THE CONDUCTORS ARE NOT THE CORRECT |
| SIZE FROM THE GENERATOR TO THE MTS PER 310.16 BASED ON |
| THE NEW 350AMP OVER CURRENT PROTECTION AS SHOWN. PLEASE |
| SEE THE 300MCM IS ONLY RATED AT 285AMPS. |
| 240.4, 310.16. |
| |
| 6) NOTE: PLEASE SEE A COMPLETE READABLE LAYOUT FOR ALL |
| EQUIPMENT, LOCATIONS, SET-BACKS ETC WAS NOT SUBMITTED. |
| THE DETAILS ON THE SHEETS ARE TOO SMALL, ARE NOT CLEAR |
| AND DO NOT PROVIDE THE LOCATIONS OF ALL EQUIPMENT. |
| AS THE NOW MTS IS NOT CLEAR IF IT IS SERVICE ENTRANCE |
| RATED DUE THE SPECS WHICH MENTIONS EQUIPMENT RATED TO |
| GO TO THE SERVICE ENTRANCE EQUIPMENT, IS THE EXISTING |
| PANEL LOCATED IN CLOSE PROXIMITY AND DOES IT CONTAIN |
| OVER CURRENT PROTECTION? |
| IS THIS MTS SERVICE ENTRANCE RATE AND CONTAIN OVER |
| CURRENT PROTECTION. THE SPECS MENTIONS FUSES AS PART OF |
| THE FEATURES HOWEVER THE NOTES ON SAME SHEET SEEM TO |
| CONTRADICT THIS. |
| PLEASE SEE 230.76, 230.79, 230.70, 71, 230.90 ETC. |
| IS THERE ANY FURTHER SPECS/CUT SHEETS WHICH INDICATE |
| THE INTERNAL WIRING AND INFORMATION ON UNIT? |
| 110.3, 90.7. |
| FBC 106.1.2, 106.3.5.1.2 |
| |
| 7) NOTE: PLEASE SEE NFPA-110 CHAPTER 7 AND BUILDING |
| CODE REQUIREMENTS WHICH REQUIRE THIS UNIT TO BE MOUNTED |
| A MINIMUM OF 6INCHES ABOVE THE BFE. THE PLANS/SHEETS |
| SUBMITTED DO NOT INDICATE THE ELEVATIONS AND SO ON. SEE |
| THE BUILDING REVIEW COMMENTS FOR THIS ALSO. |
| |
| 8) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED ARE |
| THE SAME AS SUBMITTED FROM PREVIOUS REVIEWED PLANS |
| WHICH ARE FOR A RESIDENTIAL APPLICATION. |
| PLEASE SUBMIT THE LOADS INTENDED FOR THIS UNIT AS |
| COMMERCIAL.PLEASE ALSO SEE THAT BASED ON NOW A SINGLE |
| PHASE UNIT BEING INSTALLED, THIS WILL REVISE SHEETS. |
| PLEASE COORDINATE ALL SHEETS, PLANS, ETC. |
| 220.3,220.10,220.11,220.13, 220.35 ETC |
| FBC 106.1.2 |
| |
| 9) NOTE: PLEASE SEE WHAT APPEARS TO BE THE LATEST RISER |
| DOES NOT CONTAIN AN CONDUCTOR SIZES FROM THE METER TO |
| THE MTS?? |
| PLEASE COMPLETE RISER. |
| PLEASE SEE 310.16, 240.4. |
| |
| 10) NOTE: PLEASE KNOW SINCE THERE WERE COMMENTS AND |
| PLANS HAVE FAILED THREE TIME FOR SOME OF THE SAME |
| NOTES, THE PREVIOUS REVIEW MENTIONED FS 553.80(2)(B) |
| WITH RESPECT TO REPEAT COMMENTS. A FEE IS NOW ASSESSED |
| IN THE AMOUNT OF $771.50 WHICH WILL BE REQUIRED TO BE |
| PAID BEFORE THE NEXT RE-SUBMITTAL. |
| |
| 11) NOTE: PLEASE SEE AS NOTED ON THE PREVIOUS REVIEW |
| THE NOC WILL NEED TO BE RE-RECORDED AS IT HAS EXPIRED |
| PER FS 713.13(2). |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCEA ND THESE SHEETS SHOULD BE ATTACHED IN |
| ONE SET AND LABLED OLD/VOIDED SHEETS. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |