2007-02-23 16:58:55*****UNSAT*****
 THE FOLLOWING COMMENTS FROM THE PREVIOUS FIRE PLAN
 REVIEW STILL NEED TO BE ADDRESSED.
  
  
 1.)NFPA 110 STANDARD FOR EMERGENCY AND STAND-BY POWER
 SYSTEMS, SHALL BE REFERENCED.
  
 2.)CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.)THE INSTALLATION OF THE PROPOSED EQUIPMENT SHALL
 IN NO WAY OBSTRUCT OR HINDER EMERGENCY RESPONSE TO THE
 SAID PROPERTY AND/OR VICINITY THEREOF.
  
 5.)HOW WILL THE GENERATOR BE PROTECTED FROM VEHICULAR
 (CAR AND/OR TRUCK) DAMAGE?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED.
  
  
  