Plan Review Notes
Plan Review Notes For Permit 06082000
Permit Number 06082000
Review Stop B
Sequence Number 2
Notes
Date Text
2007-02-12 18:16:19DENIED BY BUILDING
  
 1) THE GENERATOR IS 115.2 INCHES LONG. THE ONLY PAD
 LISTED ON THE ENGINEERING LARGE ENOUGH IS FRCC GEN 5.
 THE CALCULATIONS FOR THIS PAD WERE NOT PROVIDED.
  
 2)FS 471 REQUIRES EACH SHEET TO BE SIGNED AND SEALED
 OR A SIGNED AND SEALED COVER OR INDEX SHEET SPECIFING
 THE PAGES IN THE REPORT OR SPECIFICATIONS. ENGINEERING
 SUBMITTED DOES NOT COMPLY. SEE FAC 61G15-23.
  
 3)THE SIGNATURE IS REQUIRED TO BE ORIGINAL. COLOR
 PHOTO COPIES ARE NOT ACCEPTABLE. ALSO THE DATE ON THE
 ENGINEERING IS THE DATE OF WHEN THE RAISE SEAL IS
 AFFIXED. SEE FS 471.
  
 4) SUBMIT SIGNED AND SEALED PAD AND BOLT LAYOUTS AND
 CONNECTION DETAIL DRAWINGS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  