Plan Review Notes
Plan Review Notes For Permit 06082000
Permit Number 06082000
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-11 13:49:11*****UNSAT*****
  
  
  
 1.)NFPA 110 STANDARD FOR EMERGENCY AND STAND-BY POWER
 SYSTEMS, SHALL BE REFERENCED.
  
 2.)CONSTRUCTION, ALTERATION, AND DEMOLITION
 OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.)THE INSTALLATION OF THE PROPOSED EQUIPMENT SHALL
 IN NO WAY OBSTRUCT OR HINDER EMERGENCY RESPONSE TO THE
 SAID PROPERTY AND/OR VICINITY THEREOF.
  
 4.)PROVIDE MANUFACTURER SPECS SHEETS FOR THE
 GENERATOR AND ASSOCIATED EQUIPMENT.
  
 5.)HOW WILL THE GENERATOR BE PROTECTED FROM VEHICULAR
 (CAR AND/OR TRUCK) DAMAGE?
  
  
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722