Plan Review Notes
Plan Review Notes For Permit 06082000
Permit Number 06082000
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-05 00:00:00********** UNSAT *************
  
 1) NOTE: PLEASE SUBMIT PLANS WHICH
 REFLECT THE 2002 NFPA-70 (NEC), THE 2002
 NFPA-110, 2004 FBC.
  
 2) NOTE: PLEASE CORRELATE SLAB DETAIL
 AND SPECS FROM MANUFACTURE. PLEASE SEE
 SIZE INDICATED FOR THIS 80KW UNIT DOES
 NOT EXIST ON SHEETS FROM THIS
 MANUFACTURE AND HAS NOT BEEN LOCATED ON
 THEIR WEBSITE.
 PLEASE SEE NFPA-110 CHPATER 7 FOR
 MOUNTING AND LOCATIONS OF GEN..
 FBC CHAPTER 27. 2004.
 ** PLEASE SEE BUILDING REVIEW COMMENTS
 AS UNIT IS BEING PROPOSED IN A FLOOD
 ZONE "A", WHICH WILL REQUIRE UNIT AT A
 MIN OF 6" ABOVE BFE. PLEASE KNOW,
 ENGINEERING ON SLAB, FOUNDATION AND
 MOUNTING IS NEEDED AS THE INFORMATION
 SUBMITTED IS NOT SUFFICIENT.
 FBC 106.1.2
  
 3) NOTE: PLEASE SEE RISER SUBMITTED IS
 SHOWING SEC'S AND FEEDERS WHICH ARE NOT
 LARGE ENOUGH FOR THE GENERATOR FEEDERS
 OR THE 600A SERVICE BEING SHOWN.
 PLEASE SEE 240.4,310.16 AND ADJUST.
  
 4) NOTE: PLEASE SEE RISER IS SHOWING AN
 " EQUIPMENT GROUNDING CONDUCTOR" FROM
 METER TO MAIN/FIRST MEANS OF DISCONNECT
 WHICH WILL CREATE OBJECTIONAL CURRENTS. 250.6,250.24B
  
 5) NOTE: PLEASE BE SURE UNIT IS BEING
 SHOWN ON SITE/SURVEY PLANS SHOWING THE
 EXACT LOCATIONS AND SETBACKS FROM ALL
 SURROUNDING STRUCTURAL WALLS, FENCES
 ETC.
 PLEASE OBTAIN INFORMATION FROM GENERATOR MANUFACTURE
 WHICH SPECIFIES THE MIN
 CLEARENCES. PLEASE KNOW, AS THE SPEC FOR
 THE GEN WAS NOT SUBMITTED, IT IS BEING
 ASSUMED THIS UNIT IS A GENERAC UNIT, AND
 THE INFORMATION OBTAINED FROM THIS
 OFFICE IS THAT THEY REQUIRE A MIN OF 5FT
 FOR THE LARGER LIQUID COOLED UNITS.
 110.3,90.7
  
 6) NOTE: PLEASE KNOW AS TO DATE THE
 SUBMITTED GENERATOR PACKAGE MUST CONTAIN
 THE GAS INFORMATION RISER ETC, PLEASE
 SEE PLUMB REVIEW COMMENTS.
  
 7) NOTE: PLEASE PROVIDE A
 LAYOUT/OVERVIEW ON PLANS WHICH SHOWS THE
 LOCATIONS OF ALL SERVICE EQUIPMENT AS
 SHWON ON RISER DIAGRAM.
 PLEASE SEE SPECS FOR ATS DO NOT SEEM TO
 INDICATE THE NEMA RATING IF THE ATS IS
 OUTSIDE.
 PLEASE ALSO HIGH-LIGHT UNIT.
 FBC 106.1.2, 110.3
  
 8) NOTE: PLEASE SEE NO DISCONNECT
 GROUPED WITH THE EXISTING MAIN COULD BE
 LOCATED ON PLANS OR ON RISER. PLEASE SEE 225.31-225.39,
 230.72.
 PLEASE KNOW THE BREAKER LOCATED INSIDE
 THE GENERATOR IS NOT ACCEPTABLE FOR
 THIS.
 PLEASE KNOW THE ATS AS SUBMITTED DEOS
 NOT CONTAIN A MAIN DISCONNECT RATED FOR
 THE LOAD SERVED AS REQUIRED FOR THE
 FEEDERS COMING FROM THE GENERATOR. THIS
 TYPE UNIT MAY ONLY CONTAINA "TOGGLE"
 TYPE DEVICE WHICH IS NOT RATED.
  
 9) NOTE: PLEASE SUBMIT COMPLETE
 ELECTRICAL LOAD CALCULATIONS FOR THIS
 COMMERCIAL BUILDING. PLEASE SEE THE LOAD
 CALCS SUBMITTED ARE FOR A RESIDENTIAL
 HOUSE WHEN THIS IS A COMM BLDG.????
 220.3,220.10,220.11,220.13, ETC
 CONTINUOUS LOADS AT 125% 215.3,230.42
 ETC.
  
 10) NOTE: WHEN SUBMITTING PLANS/DESIGNS
 WHICH ARE NOT DONE BY AN ENGINEER,
 PLEASE SEE THAT ALL PLANS/DESIGNS MUST
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBEL FOR PLANS AND
 DESIGNS.
 FBC 106.1.2
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717