2006-09-05 00:00:00 | ********** UNSAT ************* |
| |
| 1) NOTE: PLEASE SUBMIT PLANS WHICH |
| REFLECT THE 2002 NFPA-70 (NEC), THE 2002 |
| NFPA-110, 2004 FBC. |
| |
| 2) NOTE: PLEASE CORRELATE SLAB DETAIL |
| AND SPECS FROM MANUFACTURE. PLEASE SEE |
| SIZE INDICATED FOR THIS 80KW UNIT DOES |
| NOT EXIST ON SHEETS FROM THIS |
| MANUFACTURE AND HAS NOT BEEN LOCATED ON |
| THEIR WEBSITE. |
| PLEASE SEE NFPA-110 CHPATER 7 FOR |
| MOUNTING AND LOCATIONS OF GEN.. |
| FBC CHAPTER 27. 2004. |
| ** PLEASE SEE BUILDING REVIEW COMMENTS |
| AS UNIT IS BEING PROPOSED IN A FLOOD |
| ZONE "A", WHICH WILL REQUIRE UNIT AT A |
| MIN OF 6" ABOVE BFE. PLEASE KNOW, |
| ENGINEERING ON SLAB, FOUNDATION AND |
| MOUNTING IS NEEDED AS THE INFORMATION |
| SUBMITTED IS NOT SUFFICIENT. |
| FBC 106.1.2 |
| |
| 3) NOTE: PLEASE SEE RISER SUBMITTED IS |
| SHOWING SEC'S AND FEEDERS WHICH ARE NOT |
| LARGE ENOUGH FOR THE GENERATOR FEEDERS |
| OR THE 600A SERVICE BEING SHOWN. |
| PLEASE SEE 240.4,310.16 AND ADJUST. |
| |
| 4) NOTE: PLEASE SEE RISER IS SHOWING AN |
| " EQUIPMENT GROUNDING CONDUCTOR" FROM |
| METER TO MAIN/FIRST MEANS OF DISCONNECT |
| WHICH WILL CREATE OBJECTIONAL CURRENTS. 250.6,250.24B |
| |
| 5) NOTE: PLEASE BE SURE UNIT IS BEING |
| SHOWN ON SITE/SURVEY PLANS SHOWING THE |
| EXACT LOCATIONS AND SETBACKS FROM ALL |
| SURROUNDING STRUCTURAL WALLS, FENCES |
| ETC. |
| PLEASE OBTAIN INFORMATION FROM GENERATOR MANUFACTURE |
| WHICH SPECIFIES THE MIN |
| CLEARENCES. PLEASE KNOW, AS THE SPEC FOR |
| THE GEN WAS NOT SUBMITTED, IT IS BEING |
| ASSUMED THIS UNIT IS A GENERAC UNIT, AND |
| THE INFORMATION OBTAINED FROM THIS |
| OFFICE IS THAT THEY REQUIRE A MIN OF 5FT |
| FOR THE LARGER LIQUID COOLED UNITS. |
| 110.3,90.7 |
| |
| 6) NOTE: PLEASE KNOW AS TO DATE THE |
| SUBMITTED GENERATOR PACKAGE MUST CONTAIN |
| THE GAS INFORMATION RISER ETC, PLEASE |
| SEE PLUMB REVIEW COMMENTS. |
| |
| 7) NOTE: PLEASE PROVIDE A |
| LAYOUT/OVERVIEW ON PLANS WHICH SHOWS THE |
| LOCATIONS OF ALL SERVICE EQUIPMENT AS |
| SHWON ON RISER DIAGRAM. |
| PLEASE SEE SPECS FOR ATS DO NOT SEEM TO |
| INDICATE THE NEMA RATING IF THE ATS IS |
| OUTSIDE. |
| PLEASE ALSO HIGH-LIGHT UNIT. |
| FBC 106.1.2, 110.3 |
| |
| 8) NOTE: PLEASE SEE NO DISCONNECT |
| GROUPED WITH THE EXISTING MAIN COULD BE |
| LOCATED ON PLANS OR ON RISER. PLEASE SEE 225.31-225.39, |
| 230.72. |
| PLEASE KNOW THE BREAKER LOCATED INSIDE |
| THE GENERATOR IS NOT ACCEPTABLE FOR |
| THIS. |
| PLEASE KNOW THE ATS AS SUBMITTED DEOS |
| NOT CONTAIN A MAIN DISCONNECT RATED FOR |
| THE LOAD SERVED AS REQUIRED FOR THE |
| FEEDERS COMING FROM THE GENERATOR. THIS |
| TYPE UNIT MAY ONLY CONTAINA "TOGGLE" |
| TYPE DEVICE WHICH IS NOT RATED. |
| |
| 9) NOTE: PLEASE SUBMIT COMPLETE |
| ELECTRICAL LOAD CALCULATIONS FOR THIS |
| COMMERCIAL BUILDING. PLEASE SEE THE LOAD |
| CALCS SUBMITTED ARE FOR A RESIDENTIAL |
| HOUSE WHEN THIS IS A COMM BLDG.???? |
| 220.3,220.10,220.11,220.13, ETC |
| CONTINUOUS LOADS AT 125% 215.3,230.42 |
| ETC. |
| |
| 10) NOTE: WHEN SUBMITTING PLANS/DESIGNS |
| WHICH ARE NOT DONE BY AN ENGINEER, |
| PLEASE SEE THAT ALL PLANS/DESIGNS MUST |
| CONTAIN THE PRINTED NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBEL FOR PLANS AND |
| DESIGNS. |
| FBC 106.1.2 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |