Plan Review Notes
Plan Review Notes For Permit 06082000
Permit Number 06082000
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-28 00:00:00DENIED BY BUILDING
  
 1) THE EQUIPMENT IS LOCATED IN AN "A9"
 FLOOD ZONE, AN ELEVATION CERTIFICATE
 WILL BE REQUIRED. BASE FLOOD ELEVATION
 IS 13 FEET PLUS THE ADDITIONAL .5 FEET
 REQUIRED BY CITY ORDINANCE.
  
 2) THE CLADLITE PADS LISTED ON THE
 WEBSITE ARE 4" THICK AND HAVE SMALLER
 DIMENSIONS THAN SPECIFIED ON THE SLAB
 CUT SHEET, WHICH SPECIFIES A 6" THICK
 PAD. UNDER EXCLUSIONS AND LIMITATIONS
 THE CLADLITE PADS THE MANUFACTURER
 STATES THAT THEY ARE DESIGNED FOR LIGHT
 GROUND SUPPORTED EQUIPMENT SUCH AS AIR
 CONDITIONING CONDENSERS. ANCHORAGE FOR
 UNITS OVER 36" TALL SHALL BE DESIGNED IN
 ACCORDANCE WITH FBC MECHANICAL SECTION
 301.13. SUBMIT INFORMATION FROM THE
 MANUFACTURER THAT SLAB WILL SUPPORT THIS
 GENERATOR AND CALCULATIONS FOR WIND
 LOADS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  
  