Plan Review Notes For Permit 06081982 |
Permit Number |
06081982 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-09-09 00:00:00 | | | | | DENIED | | | | 1) ENGINEERING FOR THE FOOTER SIZE HAS | | NOT BEEN SIGNED AND SEALED | | | | 2) PLEASE NOTE THAT THEIR IS A FOOTING | | SIZE TABLE ON PAGE ONE BUT WITH THE BEAM | | SPAN INDICATED A 12X12 FOOTER WITH 2- #5 | | BARS WOULD BE REQUIRED. IF YOU WISH TO | | USE THE 8X9.5 SIZE THE ENGINEER IS | | REQUIRED TO SIGN AND SEAL THE | | CALCULATION SHEET | | | | 3) A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT IS REQUIRED PRIOR TO A | | PERMIT BEING ISSUED | | | | ADRIAN MORSE | | BLDG PLAN REVIEW | | 561-805-6716 |
|