2006-08-31 00:00:00*** DENIED ***
 1) NEED TO SUBMIT ENGINEERING SHOWING
 HOW CONDENSER UNIT AND STAND ARE TO BE
 MOUNTED TO THE WALL, AND THAT IT
 COMPLIES WITH 2004 FBC 1609 (WIND LOADS)
  
 2) ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1 .
  