Plan Review Notes
Plan Review Notes For Permit 06081935
Permit Number 06081935
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-12 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT A PANEL SCHEDULE PER 408.4 NEC
 AND 106.3.5.4(8) FBC.
  
 2} PROVIDE A LOAD CALCULATION PER
 220.31, INCLUDE ADDED LOADS.
  
 3} PROVIDE A RISER DIAGRAM IF CHANGING
 THE SERVICE.
  