Plan Review Notes
Plan Review Notes For Permit 06081935
Permit Number 06081935
Review Stop B
Sequence Number 1
Notes
Date Text
2006-10-06 00:00:00BUILDING REVIEW CHECKLIST:
 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 13-101.2.2 FBC 2004.
  
 2- SITE PLAN TO HAVE ALL DIMENSIONS, INCLUDING LOT
 SIZE,TO VERIFY COMPLIANCE WITH SETBACKS AND DISTANCE
 BETWEEN BUILDINGS.
  
 3-SHEET #5:
 A) BUCK DETAILS DON'T APPLY. PROPOSED ADDITION IS
 MASONRY CONSTRUCTION. DETAILS SHOWN ARE FOR WOOD FRAMED
 WALLS. NEED DETAILS THAT MATCH PROPOSED CONSTRUCTION.
 SEE SEC. R613.62 FOR SPECIFIC WINDOW AND DOOR BUCK
 REQUIREMENTS.
 B) ALSO, MAKE SURE DETAILS ARE FOR TYPE OF WINDOW
 USED. SOME DETAILS ARE FOR CASEMENT WINDOWS. THERE ARE
 NOT CASEMENT WINDOWS. REVISE AS REQUIRED.
  
 4- SHEET #6:
 A)SIZE OF BEAM SPECIFIED ON DETAILS S-2 AND S-3
 DON'T MATCH SIZE SPECIFIED ON ROOF FRAMING PLAN. REVISE
 AS REQUIRED.
  
 B)CLARIFY DETAIL S-1.IS THIS NEW CONSTRUCTION OR
 EXISTING. DRAWINGS CALL FOR NEW FOOTING AND NEW STUDS
 AT 16". OC. REVISE/CLARIFY AS REQUIRED. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.
  
 C)THERE ARE 2 DIFFERENT DETAILS F/6.0.
 CLARIFY/REVISE AS REQUIRED. ALSO, PROVIDE ONLY THE
 DETAILS THAT APPLY TO THIS JOB AND CLEARLY KEY THEM IN
 THE FLOOR PLANS AND FRAMING PLANS.
  
 D)PROVIDE COMPLETE SPECS FOR DETAILS S-2 AND S-3:
 NEED COMPLETE WALL SPECS, INCLUDING PLYWOOD SHEATHING
 SIZE FATENER TYPE AND SPACING. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 E) SEE SIMPSONG ANCHORSSPECIFIED ON DETAILS. SEE
 CURRENT SIMPSON CATALOGUEAND UPDATE NUMBER AND TYPE
 OFFASTENERS AS REQUIRED TO MATCH PUBLISHED VALUES.
 OTHERWISE, PROVIDE COMPLETE ENGINEERING ANALYSIS IF
 NUMBERS DIFFER FROM THOSE TESTED AND PUBLISHED BY THE
 MANUFACTURER. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 F)DETAIL S-1: SPECIFY STUDS CONNECTORS AT TOP AND
 BOTTOM. SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004.
 PROVIDE COMPLETE SPECS FOR WALL INSTALLATION. SEC.
 106.2 CITY AMENDMENTS TO FBC 2004.
  
 4- SHEET #7.0: LOCATION AND NUMBEROF VERTICAL
 REINFORCEMENTS SHOWN ON THIS FOUNDATION PLANDOENS'T
 MATCHFLOOR PLAN REVISE AS REQUIRED TO MATCH EACH
 OTHER. SEC. 106.1. 2 CITY AMENDMENTS TO FBC 2004.
  
 5- SHEE 8.0:
 A)UPDATE DESIGN CRITERIA. USEFBC 2004. EDITION.
 DOORS AND WINDOWS ARE NOT IMPACT GLAZING. SEE PRODUCT
 APPROVAL SUBMITTED AND REVISE AS REQUIRED.
  
 B) ROOF SHEATHING SIZE AND TYPE SHOWN ON ROOF
 TRANSITION DETAIL DOESN'T MATCHSIZE AND TYPESHOWN
 ON ROOF NAILING NOTE. REVISE AS REQUIRED.
  
 C) MISSING DETAILE/6.0. PROVIDE DETAIL AND SPECIFY
 TRUSS CONNECTORS AT BOTH ENDS. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004.
  
 6- NOTICE OF COMENCEMENT IS EXPIRED AFTER 90 DAYS OF
 RECORDING IF WORK IS NOT STARTED. SEC. 713.13(2)
 FLORIDA STATUTES. NEED RE-RECORDED NOC.
  
 7- ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND
 APPROVED IN WRITTING AS REQUIRED BY SEC. 106.3.3 CITY
 AMENDMENTS TO FBC 2004. INCLUDING THE STORM SHUTTERS.
  
 8- ROOF TRUSSES ARE REQUIRED FOR REVIEW PRIOR TO
 INSTALLATION AS REQUIRED BY SECTION R802.10 OF 2004
 RESIDENTIAL CODE.
  
 9-ENGINEEROF RECORD TO SPECIFYROOF TILE FASTENING
 AS REQUIRED BY SEC. 106.1.1.2 CITY AMENDMENTS TO FBC
 2004.
  
 10- AS REQUIRED BY RULE 9B-72, PROVIDE FLORIDA/LOCAL
 PRODUCT APPROVAL FOR:
 A)FLAT ROOF SYSTEM. NOA 03-0212.12 SUBMITTED EXPIRED
 ON 07/19/06.
  
 B) CONCRETE LINTELS.NOA 03-0605.04 SUBMITTED IS FOR
 4", 6" & 12" WIDE LINTELS. SPECIFY ON PLANS SIZES OF
 LINTEL TO BE USED AND PROVIDE CORRECT PRODUCT
 APPROVAL.
  
 C)ALL SIMPSON TRUSS CONNECTORS SPECIFIED ON PLANS
 AND DETAILS.
  
 D)NOA FOR PGT OUTSWING ALUMINUM FRENCH DOOR THAT
 MATCHES ONE SUBMITTED FOR FLORIDA PRODUCT APPROVAL. .
 NOA 02-0625.01 SUBMITTED DOESN'T MATCH ONE SUBMITTED
 FOR FLORIDA PRODUCT APPROVAL FL253. PROVIDE MATCHING
 INFORMATION.
  
 E)NOA 02-0702.02 FOR"SH-4000" ALUMINUM SINGLE HUNG
 WINDOWS IS EXPIRED. PROVIDE CURRENT ONE.
  
 11-SOIL TEST REPORT:
 A) PROVIDE 2 COPIES WITH ORIGINAL SEAL, SIGNATURE AND
 DATE AS REQUIRED BY CHAPTER 471 FLORIDA STATUTES.
  
 B)REPORT NEEDS TO HAVE ENGINEERING FIRM CERTIFICATE
 OF AUTHORIZATION # AS REQUIRED BY ADMINISTRATIVE CODE
 61G15-23.002.
  
 12- STORM SHUTTERS:
 A) PROVIDE FLORIDA PRODUCT APPROVAL WITH 2004 CODE
 VERSION. ONE SUBMITTED IS FOR 2001.
  
 B) PROVIDE KEY PLAN AND COMPLETE INSTALLATION
 SCHEDULE. SEE ATTACHED COPY OF CITY SAMPLE FOR
 INSTALLATION SCHEDULE AND PROVIDE ALL REQUIRED
 INFORMATION.
  
 13- OWES $3.18 FOR RADON FEES.
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER