2006-09-18 00:00:00 | |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PLEASE LOCATE ALL SERVICE EQUIPMENT |
| ON THE PLAN, METER ENCLOSURE, |
| DISCONNECTS AND PANELS, SO THAT |
| COMPLIANCE WITH ARTICLES 225 AND 230 CAN |
| BE REVIEWED. |
| |
| 2} A DISCONNECTING MEANS PER 225.31, |
| LOCATED PER 225.32, AND GROUNDED PER |
| 250.32 IS REQUIRED AT THE SEPARATE |
| STRUCTURE. |
| |
| 3} PANEL "B" SCHEDULE INDICATES A 60 AMP |
| PANEL, THE RISER AND PLAN INDICARE PANEL |
| "B" IS 100 AMPS. PLEASE CORRELATE. |
| |
| 4} PLEASE VERIFY THE FEEDER AND |
| GROUND(S) SIZE AND NUMBER TO THE |
| "CABANA" PANEL. CORRECT ON PLAN. |
| |
| 5} A LIGHTING OUTLET IS REQUIRED FOR |
| EGRESS PER 210.70(A)(2)(B). NOTE THE ONE |
| AROUND THE CORNER FROM THE DOOR WILL NOT |
| MEET THE INTENT. |
| |
| 6} THE 60 AMP OCP FOR THE WATER HEATER |
| IS TO LARGE TO PROTECT THE 5000 WATT |
| LOAD. SEE 422.13 AND 240.6. |
| |
| 7} PLEASE SEE NOTE #7 REGARDING JUNCTION |
| BOXES AND REFERENCING 370.17 ARE FROM |
| THE 1996 CODE. THE CODE CURRENTLY |
| ADOPTED IS 2002 NEC. PLEASE CORRECT. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |