Plan Review Notes
Plan Review Notes For Permit 06081932
Permit Number 06081932
Review Stop E
Sequence Number 1
Notes
Date Text
2006-09-18 00:00:00 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 2} A DISCONNECTING MEANS PER 225.31,
 LOCATED PER 225.32, AND GROUNDED PER
 250.32 IS REQUIRED AT THE SEPARATE
 STRUCTURE.
  
 3} PANEL "B" SCHEDULE INDICATES A 60 AMP
 PANEL, THE RISER AND PLAN INDICARE PANEL
 "B" IS 100 AMPS. PLEASE CORRELATE.
  
 4} PLEASE VERIFY THE FEEDER AND
 GROUND(S) SIZE AND NUMBER TO THE
 "CABANA" PANEL. CORRECT ON PLAN.
  
 5} A LIGHTING OUTLET IS REQUIRED FOR
 EGRESS PER 210.70(A)(2)(B). NOTE THE ONE
 AROUND THE CORNER FROM THE DOOR WILL NOT
 MEET THE INTENT.
  
 6} THE 60 AMP OCP FOR THE WATER HEATER
 IS TO LARGE TO PROTECT THE 5000 WATT
 LOAD. SEE 422.13 AND 240.6.
  
 7} PLEASE SEE NOTE #7 REGARDING JUNCTION
 BOXES AND REFERENCING 370.17 ARE FROM
 THE 1996 CODE. THE CODE CURRENTLY
 ADOPTED IS 2002 NEC. PLEASE CORRECT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  
  
  