Plan Review Notes
Plan Review Notes For Permit 06081660
Permit Number 06081660
Review Stop M
Sequence Number 1
Notes
Date Text
2006-09-06 00:00:00*** DENIED ***
 1) SITE PLAN SHOWS A FORM BOARD
 LOCATION, PLEASE SHOW WHAT IS TO BE
 BUILT ON THET SITE.
  
 2) GENERATOR LOCATION NEEDS TO BE
 LABELED.
  
 3) PLEASE SHOW BUILDING OPENINGS ON SITE
 PLAN. GENERATOR EXHUST MUST BE TEN FEET
 AWAY FROM ANY BUILDING OPENINGS
 (WINDOWS, DOORS, ROOF & EAVE VENTS). PER
 2004 FBC/M 401.5.1 .
  
 4) GENERATOR MAY BE TO CLOSE TO
 STRUCTURE THAT WILL BE BUILT ON FORM
 BOARD LOCATION.
  
 5)NEED TO SUBMIT TWO COPIES OF ALL
 DOCUMENTS. ALL INFORMATION,
 DRAWINGS,SPECIFICATIONS AND ACCOMPANYING
 DATA SHELL BEAR THE NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE
 DESIGN. PER 2004 WPB(A) FBC 106.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  
  