Plan Review Notes For Permit 06081593 |
Permit Number |
06081593 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-11-29 12:54:53 | BUILDING REVIEW SECOND CHECKLIST: | | | | ***NOTE: COMMENTS FROM FIRST CHECKLIST WERE NOT | | ADDRESED. INFORMATION SUBMITTED ARE JUST COPIES OF | | TABLE 2304.9.1. THIS APPLIES TO ROOF SHEATHING ONLY. | | FLAT ROOF INFORMATION STILL NEEDS TO BE PROVIDED TO | | VERIFY COMPLIANCEWITH BUILDING CODE. | | | | 1- PRODUCT APPROVAL INFORMATION IS INCOMPLETE. MISSING | | THE PAGE WITH THE SPECIFIC APPROVED ASSEMBLY TO BE | | INSTALLED AND INDICATE FASTENING OPTION.SEE ATTACHED | | COPY OF CITY POLICY FOR RE-ROOFING PERMITS. | | | | 2- FLAT ROOFS USUALLY REQUIRE NAIL ENHANCING AT CORNER | | AND PERIMETER TO INCREASE THE DESIGN PRESSURES OF THE | | SYSTEM. IF SELECTED SYSTEM IS LIMITED BY GENERAL | | LIMITATION #7, THEN PROVIDE THE REQUIRED RAS 117 | | CALCULATIONS. | | IF SELECTED SYSTEM IS LIMITED BY GENERAL LIMITATION #9, | | THEN IT MAY NOT BE USED IN THIS AREA IF DESIGN | | PRESSURES OF APPROVED ASSEMBLY ARE TOO LOW. SYSTEMS | | LIMITED BY GENERAL LIMITATION #9ARE NOT ALLOWED TO | | INCREASE THE DESIGN PRESSURES. | | SEE GENERAL LIMITATION #7 AND #9 IN LAST PAGE OF DADE | | COUNTY NOA 03-0501.02 SUBMITTED. | | | | 3- NEED RECORDED NOTICE OF COMMENCEMENT. PERMIT | | #03020111 IS EXPIRED SINCE YEAR 2003. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712 |
|