2006-11-29 12:54:53BUILDING REVIEW SECOND CHECKLIST:
  
 ***NOTE: COMMENTS FROM FIRST CHECKLIST WERE NOT
 ADDRESED. INFORMATION SUBMITTED ARE JUST COPIES OF
 TABLE 2304.9.1. THIS APPLIES TO ROOF SHEATHING ONLY.
 FLAT ROOF INFORMATION STILL NEEDS TO BE PROVIDED TO
 VERIFY COMPLIANCEWITH BUILDING CODE.
  
 1- PRODUCT APPROVAL INFORMATION IS INCOMPLETE. MISSING
 THE PAGE WITH THE SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED AND INDICATE FASTENING OPTION.SEE ATTACHED
 COPY OF CITY POLICY FOR RE-ROOFING PERMITS.
  
 2- FLAT ROOFS USUALLY REQUIRE NAIL ENHANCING AT CORNER
 AND PERIMETER TO INCREASE THE DESIGN PRESSURES OF THE
 SYSTEM. IF SELECTED SYSTEM IS LIMITED BY GENERAL
 LIMITATION #7, THEN PROVIDE THE REQUIRED RAS 117
 CALCULATIONS.
 IF SELECTED SYSTEM IS LIMITED BY GENERAL LIMITATION #9,
 THEN IT MAY NOT BE USED IN THIS AREA IF DESIGN
 PRESSURES OF APPROVED ASSEMBLY ARE TOO LOW. SYSTEMS
 LIMITED BY GENERAL LIMITATION #9ARE NOT ALLOWED TO
 INCREASE THE DESIGN PRESSURES.
 SEE GENERAL LIMITATION #7 AND #9 IN LAST PAGE OF DADE
 COUNTY NOA 03-0501.02 SUBMITTED.
  
 3- NEED RECORDED NOTICE OF COMMENCEMENT. PERMIT
 #03020111 IS EXPIRED SINCE YEAR 2003.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712