2006-09-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC RFLORIDA BUILDING CODE 2004
 RESIDENTIAL
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)THE DESIGN PRESSURE SPECIFIED BY
 C-BUCK ENGINEERING FOR ZONE 3 IS LESS
 THAN SPECIFIED BY ENGINEER OF RECORD,
 SEE SHEET S103 (-140.7).EITHER REVISE
 SHEET S103 OR CHANGE ROOF SPECIFICATION.
  
 2.)PRODUCT APPROVALS ARE TO BE
 REVIEWED BY DESIGNER OF RECORD,
 FBC*106.3.3.
  
 3.)THE ENGINEERING SUBMITTED IS A
 PHOTOCOPY.THREE COPIES OF ALL
 DOCUMENTS REQUIRED AS THIS IS A RESIDENT
 INSPECTOR JOB.
  
 4.)THIS PRODUCT APPROVAL REVISED THE
 MASTER PERMIT.WHEN RESUBMITTING,
 PLEASE SUBMIT AS A REVISION TO THE
 MASTER 05090770.
  
 5.)THE ORIGINAL PERMIT WAS ISSUED WITH
 A PROVISO THAT A THIRD SET BE SUBMITTED
 FOR STAMPING FOR THE RESIDENT INSPECTOR.
 THIS HAS NOT BEEN DONE.PLEASE ADDRESS.
  