Plan Review Notes For Permit 06081578 |
Permit Number |
06081578 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-09-13 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC RFLORIDA BUILDING CODE 2004 | | RESIDENTIAL | | FBC EBFLORIDA BUILDING CODE 2004 | | EXISTING BUILDING CODE | | FBC*CITY OF WEST PALM BEACH | | AMENDMENTS TO THE FBC2004 | | | | 1.)THE DESIGN PRESSURE SPECIFIED BY | | C-BUCK ENGINEERING FOR ZONE 3 IS LESS | | THAN SPECIFIED BY ENGINEER OF RECORD, | | SEE SHEET S103 (-140.7).EITHER REVISE | | SHEET S103 OR CHANGE ROOF SPECIFICATION. | | | | 2.)PRODUCT APPROVALS ARE TO BE | | REVIEWED BY DESIGNER OF RECORD, | | FBC*106.3.3. | | | | 3.)THE ENGINEERING SUBMITTED IS A | | PHOTOCOPY.THREE COPIES OF ALL | | DOCUMENTS REQUIRED AS THIS IS A RESIDENT | | INSPECTOR JOB. | | | | 4.)THIS PRODUCT APPROVAL REVISED THE | | MASTER PERMIT.WHEN RESUBMITTING, | | PLEASE SUBMIT AS A REVISION TO THE | | MASTER 05090770. | | | | 5.)THE ORIGINAL PERMIT WAS ISSUED WITH | | A PROVISO THAT A THIRD SET BE SUBMITTED | | FOR STAMPING FOR THE RESIDENT INSPECTOR. | | THIS HAS NOT BEEN DONE.PLEASE ADDRESS. | | |
|