Plan Review Notes For Permit 06081557 |
Permit Number |
06081557 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-09-03 00:00:00 | | | | | DENIED | | | | 1) CIY OF WEST PALM BEACH REQUIRES 2 | | COPIES OF THE FLORIDA STATE PRODUCT | | APPROVAL COVER SHEETS AND THE ASSOCIATED | | DRAWINGS, EVALUATION REPORTS OR | | MIAMI-DADE NOA THAT WAS USED FOR THE | | STATE APPROVAL. PGT FL# 243-R3 AND A | | NREVISED MIAMI-DADE NOA # 03-1105.01 | | | | 2) PROVIDE GLASS TYPE BOTH WERE MARKED | | IN THE DRAWINGS AND THE DESIGN PRESSURES | | ARE DIFFERENT FOR EACH | | | | 3) THE MAX ALLOWABLE SIZE IN SQ. FT. FOR | | THE IMPACT RESISTANT WINDOWS IS 32 SQ. | | FT. THEREFORE THE OPENING SIZES LISTED | | ARE INCORRECT UNLESS THEIR IS MORE THAN | | ONE WINDOW PER OPENING . IF THIS IS THE | | CASE PLEASE GIVE THE WINDOW SIZES FOR | | EACH OPENING AND PROVIDE A PRODUCT | | APPROVAL FOR THE MULLIONS. | | | | 4) THE DESIGN PRESSURES STATED ARE | | INCORRECT THEY SHALL BE BASED ON THE | | EFFECTIVE WIND AREA OF THE WINDOW AND | | NONE ARE LARGER THAN 50 SQ. FT.IF USING | | THE CODE BOOK TABLES, SEE NOTE 1 AND | | ALSO SPECIFY IF OPENING IS IN ZONE 4 OR | | 5 | | | | ADRIAN MORSE | | BLDG PLAN REVIEW | | 561-805-6716 | | | | |
|