2006-08-18 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- PROVIDE FLORIDA OR LOCAL PRODUCT
 APPROVAL AS REQUIRED BY DCA RULE 9B-72
 FOR FLAT ROOF SYSTEM TO BE INSTALLED.
 SEE ATTACHED COPY OF CITY POLICY FOR
 RE-ROOFING PERMITS AND PROVIDE ALL THE
 INFORMATION REQUESTED.
  
 2- FLAT ROOFS ASSEMBLIES TYPICALLY
 REQUIRE NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS. READ PRODUCT APPROVAL
 GENERAL LIMITATIONS. IF GENERAL
 LIMITATION #7 REQUIRES RAS 117
 CALCULATIONS TO BE PREPARED BY ANY OF
 THE PROFESIONALS LISTED IN SUCH
 LIMITATION, THEN PROVIDE SUCH
 CALCULATIONS WITH ORIGINAL SEAL AND
 SIGNATURE. IF RAS 117 CALCULATIONS ARE
 NOT REQUIRED TO BE DONE BYREGISTERED
 PROFESSIONALS, THEN PROVIDE SUCH
 CALCULATIONS OR USE PALM BEACH COUNTY
 PRESCRIPTIVE METHOD.
 NOTE: GENERAL LIMITATION #9 DOESN'T
 ALLOW NAIL ENHANCING, THEREFORE, SYSTEM
 MAY NOT BE USED IN THIS AREA.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (5610805-6712