 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ARCHITECTS DATES ON THE SEAL,
 SHEETS E-2, DO NOT CORRELATE.
  
 2} THE GROUND RAN WITH THE FEEDER TO THE
 NEW PANEL VIOLATES 250.6, AND WOULD
 RESULT IN OBJECTIONABLE CURRENTS BETWEEN
 THE NEUTRAL AND GROUND. PLEASE REMOVE.
  
 3} NOTE THE NEW PANEL FEEDER MUST COMPLY
 WITH 230.70(A)(1), IF THE FEED IS
 OVERHEAD FROM THE METER, A DISCONNECT IS
 REQUIRED OUTSIDE, AND GROUPED PER
 230.72. PLEASE INDICATE ON THE RISER.
  
 4} THE PANEL SCHEDULE REFLECTS FOUR AIR
 HANDLERS, THE CALCULATION ONLY TWO.
 PLEASE CORRELATE.
  
 5} 210.8(A)(6)GFI'S ARE
 REQUIRED: KITCHENS;WHERE THE
 RECEPTACLES ARE INSTALLED TO SERVE THE
 COUNTERTOP SURFACES. SOME ARE MISSING ON
 THE PLAN.
  
 6} THE POOL HEATER AND PUMP SHOWN ON THE
 PLAN ARE NOT IN THE CALCULATION, PLEASE
 INCLUDE SAME.
  