Plan Review Notes For Permit 06081508 |
Permit Number |
06081508 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-28 00:00:00 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE ARCHITECTS DATES ON THE SEAL, | | SHEETS E-2, DO NOT CORRELATE. | | | | 2} THE GROUND RAN WITH THE FEEDER TO THE | | NEW PANEL VIOLATES 250.6, AND WOULD | | RESULT IN OBJECTIONABLE CURRENTS BETWEEN | | THE NEUTRAL AND GROUND. PLEASE REMOVE. | | | | 3} NOTE THE NEW PANEL FEEDER MUST COMPLY | | WITH 230.70(A)(1), IF THE FEED IS | | OVERHEAD FROM THE METER, A DISCONNECT IS | | REQUIRED OUTSIDE, AND GROUPED PER | | 230.72. PLEASE INDICATE ON THE RISER. | | | | 4} THE PANEL SCHEDULE REFLECTS FOUR AIR | | HANDLERS, THE CALCULATION ONLY TWO. | | PLEASE CORRELATE. | | | | 5} 210.8(A)(6)GFI'S ARE | | REQUIRED: KITCHENS;WHERE THE | | RECEPTACLES ARE INSTALLED TO SERVE THE | | COUNTERTOP SURFACES. SOME ARE MISSING ON | | THE PLAN. | | | | 6} THE POOL HEATER AND PUMP SHOWN ON THE | | PLAN ARE NOT IN THE CALCULATION, PLEASE | | INCLUDE SAME. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | | | | | | | |
|