Plan Review Notes For Permit 06081399 |
Permit Number |
06081399 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-09-01 00:00:00 | | | | | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THERE MUST BE A DISCONNECT FROM THE | | GENERATOR WHERE THE CONDUCTORS ENTER THE | | BUILDING. IF ALL DISCONNECTS CANNOT BE | | GROUPED PER 230.72, SEE THAT ALL | | ARTICLES FROM 225.31 THROUGH 225.39, ARE | | COMPLIED WITH. | | | | 2} 700.15 LOADS ON EMERGENCY BRANCH | | CIRCUITS. | | NO APPLIANCES AND NO LAMPS, OTHER THAN | | THOSE SPECIFIED AS REQUIRED FOR | | EMERGENCY USE, SHALL BE SUPPLIED BY | | EMERGENCY LIGHTING CIRCUITS. PROVIDE A | | PANEL SCHEDULE FOR THE | | EMERGENCY/GENERATOR PANEL. | | | | 3} THE PERSON TAKING RESPONSIBILITY FOR | | THE PLAN/DRAWINGS, SHALL PRINT AND SIGN | | THEIR NAME ON THE SHEETS THEY DRAW. | | PLEASE DO THIS PRIOR TO RESUBMITTING. | | | | 4} PLEASE LOCATE ALL SERVICE EQUIPMENT | | ON THE PLAN, METER ENCLOSURE, | | DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN | | BE REVIEWED. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] |
|