2006-09-01 00:00:00 
  
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THERE MUST BE A DISCONNECT FROM THE
 GENERATOR WHERE THE CONDUCTORS ENTER THE
 BUILDING. IF ALL DISCONNECTS CANNOT BE
 GROUPED PER 230.72, SEE THAT ALL
 ARTICLES FROM 225.31 THROUGH 225.39, ARE
 COMPLIED WITH.
  
 2} 700.15 LOADS ON EMERGENCY BRANCH
 CIRCUITS.
 NO APPLIANCES AND NO LAMPS, OTHER THAN
 THOSE SPECIFIED AS REQUIRED FOR
 EMERGENCY USE, SHALL BE SUPPLIED BY
 EMERGENCY LIGHTING CIRCUITS. PROVIDE A
 PANEL SCHEDULE FOR THE
 EMERGENCY/GENERATOR PANEL.
  
 3} THE PERSON TAKING RESPONSIBILITY FOR
 THE PLAN/DRAWINGS, SHALL PRINT AND SIGN
 THEIR NAME ON THE SHEETS THEY DRAW.
 PLEASE DO THIS PRIOR TO RESUBMITTING.
  
 4} PLEASE LOCATE ALL SERVICE EQUIPMENT
 ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN
 BE REVIEWED.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]