Plan Review Notes For Permit 06081397 |
Permit Number |
06081397 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-10-20 07:58:38 | | | | | DENIED | | | | 1) PLEASE NOTE THE CORRECTION MADE TO PLAN AS PREVIOUS | | COMMENT REGUARDING SHUTTER SPAN WAS NOT CORRECTED, | | PANEL CANNOT BE MOUNTED HORIZONTALLY BECAUSE IT WOULD | | EXCEED THE MAXIMUM ALLOWABLE SPAN FOR THE PRESSURE | | SHOWN (MAX SPAN 85") OPENING IS 93" + 6" EDGE DISTANCE | | = 99" THEREFORE PANEL SHALL BE INSTALLED VERTICALLY | | | | 2) ALSO THE SHUTTER SPANSON THE SCHEDULE INDICATE | | THAT THE PANELS ARE MOUNTED HORIZONTALLY AS THEY ARE 2" | | LARGER THAN THE WIDTH PLEASE VERIFY THIS | | | | 3) PRODUCT APPROVALS SHOW AN EDGE DISTANCE OF 31/2" | | THEREFORE THE PANEL LENGTH/SPANS SHOULD BE APPROX 7" | | LARGER THAN THE OPENING SIZE (HORZ FOR WIDTH VERT FOR | | HEIGHT) | | | | 4) PER 713.13(2) F.S. | | IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT | | COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS | | VOID | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | |
|