Plan Review Notes
Plan Review Notes For Permit 06081397
Permit Number 06081397
Review Stop B
Sequence Number 2
Notes
Date Text
2006-10-20 07:58:38 
  
 DENIED
  
 1) PLEASE NOTE THE CORRECTION MADE TO PLAN AS PREVIOUS
 COMMENT REGUARDING SHUTTER SPAN WAS NOT CORRECTED,
 PANEL CANNOT BE MOUNTED HORIZONTALLY BECAUSE IT WOULD
 EXCEED THE MAXIMUM ALLOWABLE SPAN FOR THE PRESSURE
 SHOWN (MAX SPAN 85") OPENING IS 93" + 6" EDGE DISTANCE
 = 99" THEREFORE PANEL SHALL BE INSTALLED VERTICALLY
  
 2) ALSO THE SHUTTER SPANSON THE SCHEDULE INDICATE
 THAT THE PANELS ARE MOUNTED HORIZONTALLY AS THEY ARE 2"
 LARGER THAN THE WIDTH PLEASE VERIFY THIS
  
 3) PRODUCT APPROVALS SHOW AN EDGE DISTANCE OF 31/2"
 THEREFORE THE PANEL LENGTH/SPANS SHOULD BE APPROX 7"
 LARGER THAN THE OPENING SIZE (HORZ FOR WIDTH VERT FOR
 HEIGHT)
  
 4) PER 713.13(2) F.S.
 IF THE IMPROVEMENT DESCRIBED IN THE NOC HAS NOT
 COMMENCED WITHIN 90 DAYS OF RECORDING THE NOTICE IS
 VOID
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  