Plan Review Notes
Plan Review Notes For Permit 06081397
Permit Number 06081397
Review Stop B
Sequence Number 1
Notes
Date Text
2006-08-27 00:00:00 
  
 DENIED
  
 1)PROVIDE LOCATION OF OPENING WITH
 CLEAR PANELS AND THE DIRETION THAT THE
 PANELS WILL RUN. BE AWARE THAT THE MAX
 PANEL LENGTHS FOR CLEAR PANELS WITH
 PRESSURES OVER -40 ARE ALL BELOW 8'-0"
 FOR EXAMPLE OPENING #16 HORIZONTAL LEGTH
 IS 95" THE PRESSURE IS -53.48 THE MAX
 PANEL LENGTH IS 7'-2" OR 85" THEREFORE
 IT WILL NOT WORK
  
 2)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716