Plan Review Notes For Permit 06081397 |
Permit Number |
06081397 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-08-27 00:00:00 | | | | | DENIED | | | | 1)PROVIDE LOCATION OF OPENING WITH | | CLEAR PANELS AND THE DIRETION THAT THE | | PANELS WILL RUN. BE AWARE THAT THE MAX | | PANEL LENGTHS FOR CLEAR PANELS WITH | | PRESSURES OVER -40 ARE ALL BELOW 8'-0" | | FOR EXAMPLE OPENING #16 HORIZONTAL LEGTH | | IS 95" THE PRESSURE IS -53.48 THE MAX | | PANEL LENGTH IS 7'-2" OR 85" THEREFORE | | IT WILL NOT WORK | | | | 2)A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT IS REQUIRED PRIOR TO | | A PERMIT BEING ISSUED | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 |
|