2006-08-21 00:00:00 | |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. |
| |
| 2} THE PERSON TAKING RESPONSIBILITY FOR |
| THE DESIGN MUST PRINT AND SIGN THEIR |
| NAME TO SAME PER 106.3.4.2. |
| |
| THIS APPLICATION WAS GIVEN TO THE |
| CHIEF ELECTRICAL INSPECTOR TO DETERMINE |
| COMPLIANCE WITH ARTICLE 230.2 2002 NEC. |
| |
| THE CHIEF ELECTRICAL INSPECTOR WILL NOT |
| GRANT PERMISSION TO ADD AN ADDITIONAL |
| SERVICE TO THIS BUILDING WITHOUT THE |
| APPLICANT SHOWING CAUSE UNDER 230.2(A) |
| THROUGH (D). A COMPLETE LOAD CALCULATION |
| FOR THE EXISTING SERVICE, INCLUDING |
| CALCULATIONS ON ALL SEPARATE BUSINESSES, |
| ON THE SERVICE NOW SUPPLYING THE UNIT. |
| |
| A VOLTAGE DROP CALCULATION IS ALSO |
| REQUIRED TO BE SUBMITTED, FROM FPL VAULT |
| TO THE FIRST OVERCURRENT DEVICE ON THE |
| LOAD SIDE OF THE METER IF GRANTED |
| PERMISSION TO INSTALL. |
| |