Plan Review Notes
Plan Review Notes For Permit 06081144
Permit Number 06081144
Review Stop E
Sequence Number 1
Notes
Date Text
2006-08-21 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} THE PERSON TAKING RESPONSIBILITY FOR
 THE DESIGN MUST PRINT AND SIGN THEIR
 NAME TO SAME PER 106.3.4.2.
  
 THIS APPLICATION WAS GIVEN TO THE
 CHIEF ELECTRICAL INSPECTOR TO DETERMINE
 COMPLIANCE WITH ARTICLE 230.2 2002 NEC.
  
 THE CHIEF ELECTRICAL INSPECTOR WILL NOT
 GRANT PERMISSION TO ADD AN ADDITIONAL
 SERVICE TO THIS BUILDING WITHOUT THE
 APPLICANT SHOWING CAUSE UNDER 230.2(A)
 THROUGH (D). A COMPLETE LOAD CALCULATION
 FOR THE EXISTING SERVICE, INCLUDING
 CALCULATIONS ON ALL SEPARATE BUSINESSES,
 ON THE SERVICE NOW SUPPLYING THE UNIT.
  
 A VOLTAGE DROP CALCULATION IS ALSO
 REQUIRED TO BE SUBMITTED, FROM FPL VAULT
 TO THE FIRST OVERCURRENT DEVICE ON THE
 LOAD SIDE OF THE METER IF GRANTED
 PERMISSION TO INSTALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]