Plan Review Notes
Plan Review Notes For Permit 06081123
Permit Number 06081123
Review Stop G
Sequence Number 1
Notes
Date Text
2006-08-21 00:00:00******DENIED*****
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR GAS PLAN REVIEW ON THE ISOMETRIC
 DRAWING FOR A PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. PLEASE INDICATE ON THE
 ISOMETRIC DRAWING EXISTING AND NEW.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 PLEASE INDICATE ON THE DRAWING IF THE
 GALVANIZED PIPE IS ABOVE OR BELOW
 GROUND. NOTE: GALVANIZED PIPE BELOW
 GROUND IS UNACCEPTABLE PER FBC-2004,
 FUEL GAS, SECTION 404.8.
  
 3. TYPE OF GAS, (LP OR NATURAL) PLEASE
 INDICATE ON DRAWING.
  
 4. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33). (NOTE: TOTAL BTU LOAD
 INCLUDING EXISTING NEEDS TO BE INDICATED
 ON DRAWING. PLEASE REFERENCE ATTACHED
 PERMIT INFORMATION SHEET INDICATING SAID
 ADDRESS HAS EXISTING GAS.)
  
 5. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4). (NOTE: THIS
 INCLUDES THE EXISTING GAS SYSTEM IF
 APPLICABLE.)
  
 6. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2 (NOTE:
 IF SYSTEM IS A 2LB SYSTEM MANUFACTURER
 CUT SHEETS OF REGULATORS REQUIRED.
 MANUFACTURER CUT SHEETS OF POOL HEATER
 REQUIRED TO VERIFY BTU'S.)
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
 9. THE FOLLOWING INFORMATION IS REQUIRED
 ON THE SUBMITTED BOUNDARY SURVEY.
 (A) LOCATION OF GAS METER
 (B) LOCATION OF POOL HEATER
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved