Date |
Text |
2006-08-21 00:00:00 | ******DENIED***** |
| REFERENCE: FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR GAS PLAN REVIEW ON THE ISOMETRIC |
| DRAWING FOR A PERMIT: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. PLEASE INDICATE ON THE |
| ISOMETRIC DRAWING EXISTING AND NEW. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| PLEASE INDICATE ON THE DRAWING IF THE |
| GALVANIZED PIPE IS ABOVE OR BELOW |
| GROUND. NOTE: GALVANIZED PIPE BELOW |
| GROUND IS UNACCEPTABLE PER FBC-2004, |
| FUEL GAS, SECTION 404.8. |
| |
| 3. TYPE OF GAS, (LP OR NATURAL) PLEASE |
| INDICATE ON DRAWING. |
| |
| 4. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). (NOTE: TOTAL BTU LOAD |
| INCLUDING EXISTING NEEDS TO BE INDICATED |
| ON DRAWING. PLEASE REFERENCE ATTACHED |
| PERMIT INFORMATION SHEET INDICATING SAID |
| ADDRESS HAS EXISTING GAS.) |
| |
| 5. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). (NOTE: THIS |
| INCLUDES THE EXISTING GAS SYSTEM IF |
| APPLICABLE.) |
| |
| 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| |
| 7. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2 (NOTE: |
| IF SYSTEM IS A 2LB SYSTEM MANUFACTURER |
| CUT SHEETS OF REGULATORS REQUIRED. |
| MANUFACTURER CUT SHEETS OF POOL HEATER |
| REQUIRED TO VERIFY BTU'S.) |
| |
| 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| 9. THE FOLLOWING INFORMATION IS REQUIRED |
| ON THE SUBMITTED BOUNDARY SURVEY. |
| (A) LOCATION OF GAS METER |
| (B) LOCATION OF POOL HEATER |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |